REMKO SuperTec-Monitor User Manual
Page 19
Setting on SW2
System component
Measuring range and description
Unit
Switch-on duration until
fault
0 – 999
0 – 999
If the duration is over 99 min.,
the display switches
between the 100s digit, the
10s and 1s digits, and
2 spaces.
Example: 415 min.:
Minutes
ON
1 2 3 4 5 6
U9: Fault status during the
fault
00 No fault
01 Voltage too high
(voltage board)
02 Voltage too low
(control board)
04 L-phase fault
(control board)
08 Operating signal fault
(voltage board)
10 PFC fault
-Overvoltage
-Undervoltage
-Overcurrent
(voltage board)
20 PFC/ACTM fault
-Undervoltage
(check wiring from CNAF,
ACTM defective
Examples of multiple faults:
03 Overvoltage (01) and und-
ervoltage (02)
0A Under voltage (02) and
operating signal fault (08)
14 L-phase fault (04) and PFC
fault (10)
Code
ON
1 2 3 4 5 6
0.5 s
0.5 s
2 s
„ 4“ „15“ „ “
19