Remko system monitor, For remko supertec inverter – REMKO SuperTec-Monitor User Manual
Page 16

Setting on SW2
System component
Measuring range and description
Unit
DC bus voltage
CMF 80/90/140/150
CMT 100/150
180 - 370
180 – 370
If the voltage is over 99 V, the
display switches
between the 100s digit1
and the 10s and 1s digits.
°C
ON
1 2 3 4 5 6
Fan speed before fault
0 – 10
0 – 10
Levels /
Steps
ON
1 2 3 4 5 6
Fault on the temperature sen-
sor
If no temperature sensor fault
has occurred,
"—" appears on the
LED display.
3 = Liquid line on the
outdoor unit TH3, TH32
6 = two-phase line
(condenser/vaporiser)
on the outdoor unit TH6
7 = Outdoor air temperature
TH7
8 = Cooling fin temperature
sensor TH8
Code
ON
1 2 3 4 5 6
Condenser operating frequency
before fault
0 – 255
0 – 255
If the operating frequency is
over 99 H�, the display
switches between the 100s
digit, the 10s and 1s digits,
and 2 spaces.
Example: 125 H�:
H�
ON
1 2 3 4 5 6
0.5 s
0.5 s
2 s
„ 1“ „25“ „ “
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
16