Remko system monitor, For remko supertec inverter – REMKO SuperTec-Monitor User Manual
Page 10

Setting on SW2
System component
Measuring range and description
Unit
Condenser operating time
0 – 9999
0 – 9999
If the number is above 99, the
display switches between
the 100s digit, the 10s and 1s
digits, and 2 spaces.
Example: 245:
0.5 s
0.5 s
2 s
„ 2“ „45“ „ “
10 hrs
ON
1 2 3 4 5 6
Operating current of the con-
denser
0 – 50
0 – 50 (without decimal places)
A
ON
1 2 3 4 5 6
Opening width of the LEV-A
0 – 480
0 – 480
If the opening width of the
LEV-A is over 99 impulses,
the display switches between
the 100s digit, the 10s and 1s
digits, and 2 spaces.
Ex-
ample: 150 impulses:
0.5 s
0.5 s
2 s
„ 1“ „00“ „ “
Impulses
ON
1 2 3 4 5 6
Condenser operating frequency
0 – 225
0 – 225
If the condenser operating
frequency is over 99,
the display switches between
the 100s digit, 10s and 1s dig-
its, and 2 spaces.
Example: 125 H�:
0.5 s
0.5 s
2 s
„ 1“ „25“ „ “
H�
ON
1 2 3 4 5 6
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
10