beautypg.com

Annual performance number for cmf 320 duo, Climatic region: -10°c, Climatic region: -12°c – REMKO CMF 320 Duo User Manual

Page 51: Climatic region: -14°c, Climatic region: -16°c

background image

Climatic region: -10°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,44

4,30

4,16

4,11

3,96

3,80

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,34

4,20

4,05

4,00

3,85

3,69

Climatic region: -12°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,34

4,20

4,06

4,01

3,87

3,72

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,24

4,10

3,95

3,91

3,76

3,61

Climatic region: -14°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,27

4,13

4,00

3,96

3,72

3,68

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,17

4,03

3,89

3,85

3,71

3,56

Climatic region: -16°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,14

4,01

3,88

3,84

3,71

3,57

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF 320

2,5

3,9

4,4

4,02

3,89

3,76

3,72

3,58

3,44

Note: A differential of 7K has a standard floor-heating layout, a differential of 10K is typical for a radiator system

Additional key data: a heating-threshold temperature of 15°C for old construction and 12°C in new construction, a differential at the condenser

(test-bench measurements: 5K)

Annual performance number for CMF 320 Duo

Mode: bivalent-parallel with a switch-over point of -3°C

51