beautypg.com

Control panel – REMKO CMF 320 Duo User Manual

Page 25

background image

Control panel

Mode switch

Position I: Normal operation

This switch turns on the system. The heat pump

and a possible 2nd heat source (6 kW E-heater or boiler),

load- and weather-dependent, are

turned on and off - as well as regulated - automatically.

Position 0: OFF

Position II: Emergency-heat operation

This switch directly turns on all circulation pumps and the

2. heat source (9 kW E-heater or boiler),

bypassing the heat-pump manager.

Use this position only if a serious malfunction of

the heat pump occurs (e.g.: a fault in the outdoor module or

in the heat-pump manager). This function might also be helpful

if heat is ever required and the

outdoor module has not yet been installed or

or placed in service.

Green indicator light

Outdoor module A is activated

Heat pump manager

(control-and-display unit)

Red indicator light

Outdoor-module A failure

Make sure that no weather-driven control occurs
during emergency-heat operation. Therefore, limit
the inlet temperature at the controller for the
electric booster heater or at the external controller
for the boiler to a maximum temperature matched
to the boiler.
(e.g.: 55 °C for floor heating-systems)!

!

CAUTION

When the heat pump is switched off (position
0 on the function switch), the heating system is
switched off. There is no frost protection function.

NOTE

Green indicator light

Outdoor module B is activated

Red indicator light

Outdoor-module B failure

25