REMKO CMF - DUO

Leg

Leg

Foundation

Foundation

Condensate drainage-heating

Condensate drainage-heating

Drainage channel

Drain pipe

Soil

Soil

Gravel layer for

seepage

Condensation catch pan

Floor bracket

Condensation catch pan

Floor bracket

Condensate draining and
ensured discharge

Condensate connection

If the temperature falls below the
dew point, condensation will form
on the finned condenser during
heating operation.

A condensate drip pan should be
installed on the underside of the
unit to drain any condensate.

The condensate drain pipe to
be installed on-site must be in-
stalled with a in cline of at least
2 % for good drainage.
If necessary, fit vapour density
insulation.

When operating the system at
outdoor temperatures below
4 °C, care must be taken that
the condensate line is frost
protected. The lower part of the
housing and condensate pan
are to be kept frost free in order
to ensure permanent drainage
of the condensate.
If necessary, fit supplementary
pipe heating.

After completed installation,
check that the condensate
drainage is unobstructed and
ensure that the line is leak tight.

Ensured discharge in the event of
leakage

Local regulations or environ-

mental laws, for example the

German Water Resource Law

(WHG), can require suitable

precautions to protect against

uncontrolled draining in case

of leakage to provide for safe

disposal of escaping refrigera-

tor oil or hazardous media.