Wind
The site for the outdoor
module must be selected
so that machinery noise that
occurs disturbs neither the
residents nor the facility
operator. Observe the TA-
noise specifications as well
as the table containing the
drawings relating to sound
pressure levels on page 45!
NOTE
Assessment level in
accordance with TA
noise
Point of emissions
days
nights
Industrial areas
dB(A)
70
70
Commercial areas
dB(A)
65
50
Core areas, village areas and mixed zones
dB(A)
60
45
General residential areas and small housing estates dB(A)
55
40
Exclusively residential areas
dB(A)
50
35
Spa areas, hospitals and mental institutions
dB(A)
45
35
Isolated noise peaks of short dura-
tion may not exceed 30 dB(A) dur-
ing the day and 20 dB(A) at night.
Snow + 20 cm
j
Positioned side-by-side next to a wall, air outlet open to the front, flow restriction behind
k
Positioned side-by-side next to a wall, air outlet impaired to the front, flow restriction in front and behind
l
Positioned back-to-back; air outlet open to the front
k
l
j
Minimum distances in mm for the outdoor units and in brackets for the CMF 320 Duo
depending on the enclosure