Technical data
Range
CMF 80
CMF 90
CMT 100
CMF 140
CMF 150
CMT 150
confi guration
Heating only
Heating / cool-
ing
Heating / cool-
ing
Heating only
Heating / cool-
ing
Heating / cool-
ing
Inverter technology
REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec
System
Air / water
Air / water
Air / water
Air / water
Air / water
Air / water
Heat pump manager
Multitalent
Multitalent
Multitalent
Multitalent
Multitalent
Multitalent
Storage tank for hydraulic decou-
pling of volumetric fl ows
optional
optional
150 l
optional
optional
150 l
Electric booster heating 6 kW
optional
optional
Series
optional
optional
Series
Water heating
optional
optional
optional
optional
optional
optional
Heating output min / max
kW
3,5 - 10,2
3,5 - 10,2
3,5 - 10,2
5,0 - 16,0
5,0 - 16,0
5,0 - 16,0
Cooling performance min / max kW
3,3 - 8,1
3,3 - 8,1
5,5 - 14,0
5,5 - 14,0
Heating output for A7/W35
kW/COP
1)
8,1 / 4,5
8,1 / 4,5
8,1 / 4,5
14,2 / 4,5
14,2 / 4,5
14,2 / 4,5
Heating output for A2/W35
kW/COP
1)
7,0 / 3,9
7,0 / 3,9
7,0 / 3,9
13,4 / 4,2
13,4 / 4,2
13,4 / 4,2
Heating output for A7/W45
kW/COP
1)
7,3 / 3,2
7,3 / 3,2
7,3 / 3,2
13,1 /3,4
13,1 /3,4
13,1 /3,4
Heating output for A2/W45
kW/COP
1)
6,3 / 2,8
6,3 / 2,8
6,3 / 2,8
12,7 / 3,2
12,7 / 3,2
12,7 / 3,2
Heating output for A7/W55
kW/COP
1)
7,0 / 2,3
7,0 / 2,3
7,0 / 2,3
12,1 / 2,6
12,1 / 2,6
12,1 / 2,6
Heating output for A7/W55
kW/COP
1)
6,0 / 2,1
6,0 / 2,1
6,0 / 2,1
11,6 / 2,4
11,6 / 2,4
11,6 / 2,4
Functional range heating
2)
°C
-20 to +34
-20 to +34
-20 to +34
-20 to +34
-20 to +34
-20 to +34
Functional range cooling
2)
°C
+15 to +46
+15 to +46
+15 to +46
+15 to +46
+15 to +46
+15 to +46
Max. supply temperature heating water
°C
up to +55
up to +55
up to +55
up to +55
up to +55
up to +55
Refrigerant / basic fi lling
-- / kg
R 410A
3)
/ 3,5 R 410A
3)
/ 3,5 R 410A
3)
/ 3,5 R 410A
3)
/ 5.0 R 410A
3)
/ 5,0 R 410A
3)
/ 5,0
Refrigerant, additional quantity
30-50m
g/m
60
60
60
60
60
60
Power supply
V / Hz
230/1~ / 50
230/1~ / 50
230/1~ / 50
400/3~N/50
400/3~N/50
400/3~N/50
Starting current
A
12,5
12,5
12,5
8
8
8
Rated current
A
13
13
13
13
13
13
Rated capacity
kW
3,0
3,0
3,0
9,0
9,0
9,0
Customer's fuse protection (outdoor
unit)Tripping characteristic B
A
25
25
25
3x16
3x16
3x16
Volumetric fl ow water hot water at
∆t 5 K
m³/h
1,4
1,4
1,4
2,2
2,2
2,2
Pressure loss on liquefi er at ∆t 5 K kPa
5,4
5,4
5,4
8,1
8,1
8,1
Pressure loss on indoor module
kPa
11,1
11,1
22,7
22,7
max. airfl ow volume outdoor
module
m³/h
1.900
1.900
1.900
3.530
3.530
3.530
Max. permissible operating pres-
sure hot water
bar
3,0
3,0
3,0
3,0
3,0
3,0
Hydraulic connection supply /
return fl ow
Inches
1“ AG
1“ AG
1“ AG
1“ AG
1“ AG
1“ AG
Noise output LpA 1m (outdoor
unit)
dB(A)
46/38
4)
46/38
4)
46/38
4)
50/42
4)
50/42
4)
50/42
4)
Dimension indoor unit Height /
width / depth
mm
800 / 550 / 550 800 / 550 / 550 1800 / 550 / 550 800 / 550 / 550 800 / 550 / 550 1800 / 550 / 550
Dimension outdoor unit Height /
width / depth
mm
945 / 950 / 330 945 / 950 / 330 945 / 950 / 330 1350 / 950 / 330 1350 / 950 / 330 1350 / 950 / 330
Weight indoor module
kg
52
52
135
55
55
138
Weight outdoor module
kg
75
75
75
130
130
130
1) COP=coeffi cient of performance according to EN 14511
2) Based on the outdoor temperature
3) Contains greenhouse gas according to Kyoto protocol
4) Distance 5 m clear fi eld.
43