REMKO CMF-80 v.2 User Manual
Page 19
If an electricity tariff has been selected without energy
supply company shut-off, then a bridge is to be cre-
ated between terminals X1.5 and X1.6.
If an electricity tariff with energy supply company
shut-off is selected, then the customer is to arrange
for an on-site starter contact for terminals X1.5 and
X1.6. Likewise, the supply line for the outdoor mod-
ule requires an interruption mechanism installed by
the customer in accordance with the energy supply
company's off-periods. In this case it is necessary to
have a separate supply line for the indoor unit! The
booster heating system requires a separate supply line
with fuse protection in the switching cabinet con-
nected to contactor terminal K1.
Terminal assignment diagram for models CMF 80 and CMF 140
Terminal
Connection
X1.1
Supply line L
X1.2
Supply line N
X1.3
Supply line PE
X1.4
Live phase L
X1.5
Energy supply company release contact
X1.6
Energy supply company release contact
X1.7
Flow monitor
X1.8
Flow monitor
X1.9
Connection cable PE
X1.10
Connection cable S3
X1.11
Connection cable S2
X1.12
Connection cable S1
X1.13
Pump heating circuit 1 L
X1.14
Pump heating circuit 1 N
X1.15
Pump heating circuit 1 PE
X1.16
Pump heating circuit 2 L
X1.17
Pump heating circuit 2 N
X1.18
Pump heating circuit 2 PE
X1.19
Charging pump / switching valve L
X1.20
Charging pump / switching valve N
X1.21
Charging pump / switching valve PE
X1.22
Mixer heating circuit 2 open
X1.23
Mixer heating circuit 2 N
X1.24
Mixer heating circuit 2 PE
X1.25
Mixer heating circuit 2 close
X1.26
X1.27
X1.28
Release heating appliance 2 com
X1.29
Release heating appliance 2 NC
X1.30
Release heating appliance 2 NO
X1.31
Circulating pump (collector pump) L
X1.32
Circulating pump (collector pump) N
X1.33
Circulating pump (collector pump) PE
X1.34
Condenser pump L
X1.35
Condenser pump N
X1.36
Condenser pump PE
Terminal
Connection
X2.1
BUS H
X2.2
BUS +
X2.3
BUS L
X2.4
BUS -
X2.5
0 - 10 V -
X2.6
0 - 10 V +
X2.7
Return sensor / F17
X2.8
Switch input / F15
X2.9
Collector sensor / F 14 (PT 1000)
X2.10
F 13
X2.11
Storage tank sensor lower / F 12
X2.12
Supply sensor heating circuit 1 / F11
X2.13
F 1
X2.14
F 2
X2.15
F 3
X2.16
Supply sensor heating circuit 2 / F5
X2.17
Domestic water sensor / F6
X2.18
Collector sensor / F8
X2.19
External sensor / F9
X2.20
Sensor liquid line
X2.21
Sensor liquid line
X2.
Earth contact sensor
19