Accessories
Dust filter Type FK
for duct inlet
Duct filter with easy to change insertion filters with the filter class G3.
Further filter classes are available on request.
Any unused air inlet openings must be closed with appropriate metal
plates.
Dim.
in mm
VRS
25
VRS
50
VRS
75
VRS
100
VRS
130
VRS
170
VRS
200
VRS
270
VRS
340
VRS
440
VRS
540
G
485
485
485
485
545
630
630
695
695 1060 1060
K
465
660
660
765
895 1085 1085 1170 1170 1620 1620
Y
480
480
480
480
690
690
690
530
530
605
605
Z
30
30
30
30
30
30
30
30
30
35
35
Shutter flaps Type JK
Shutter flaps in galvanised metal housing with connection frame.
The torsionally stiff aluminium flaps can be continuously adjusted via
hand lever or electric shutter motor (accessory).
Combined flaps for controlling recirculating air/outside air conditions are
connected with linkages working in opposite directions.
Combination options:
Pos. I + II
Pos. I + IV
Pos. I + III
Pos. II + IV
Pos. II + III
Pos. III + IV
Any unused air inlet openings must be closed with appropriate metal
plates.
Dim.
in mm
VRS
25
VRS
50
VRS
75
VRS
100
VRS
130
VRS
170
VRS
200
VRS
270
VRS
340
VRS
440
VRS
540
G
485
485
485
485
545
630
630
695
695 1060 1060
K
465
660
660
765
895 1085 1085 1170 1170 1620 1620
Y
120
120
120
120
120
120
120
180
180
180
180
Z
30
30
30
30
30
30
30
30
30
35
35
Technical data
VRS
25
VRS
50
VRS
75
VRS
100
VRS
130
VRS
170
VRS
200
VRS
270
VRS
340
VRS
440
VRS
540
Filter area in m
2
0.72 0.96 1.36 1.76 2.16 2.88 2.88 4.82 4.82 9.18 9.18
Flow in in m/s
0.65 0.98 1.06 1.08 1.13 1.18 1.33 1.52 1.67 1.94 2.12
Initial pressure loss about 100 Pa at standard pressure and 2-sided air intake.
With a change of filter class, the changed pressure loss must be taken into account!