400V type heaters

The connection of a room thermo-

he connection of a room thermo-

stat or a day/night temperature
control takes place for these types
at the respective terminal strips in
the control box.

Connection must be carried out as
follows:

Remove the factory cable link and
connect the wires of the respective
control unit to the terminals.

The separate wiring diagrams of
the control unit and appliance
must be observed!

400 V direct and Y /

Δ starting

Terminal strip X2

The burner must be set to the

full heat load of the appliance.

The combustion chamber must

not be overloaded
(increased condensate forma-
tion).

The exhaust fume temperature

should be about 180 Kelvin
above room temperature.
There is otherwise the risk
of increased condensate
formation

!

The separate operating instruc-

tions of the factory supplied
burner must be observed.

When using forced-air burners

of other manufacturers, their
suitability for the appliance
must be verified (hot air heater
type).

Gas connection

A sufficient gas volume and gas
pressure corresponding to the
power of the heating appliance
must constantly be available whilst
the appliance is in use.

Installation of the gas connec-

tion must only be carried out by
authorised specialists.

To be observed are DIN 4756

or the DVGW worksheet G 600
for gas-fired hot air heaters and
TRF for liquid gas.

Gas pressure regulating devices

and shut-off valves must be
provided on site.

The cable cross-section must

be dimensioned, taking into
account the installed load of the
appliance, total line resistance
and gas pressure.

factory cable

link

1 2

NOtE

Prior to initial use, the gas
supply pipe must be cleaned
thoroughly and checked for
leaks!

Fuel oil connection

A sufficient and correct fuel supply
must be ensured.

The suction pipe must be provi-

ded with a foot valve in the fuel
oil tank.

Free flowing fuel oil must be

available in sufficient quantity
also at low outside tempera-
tures.
Paraffin formation can occur
already from about 5°C depen-
ding on the fuel oil quality.
Appropriate measures must be
taken to prevent this occurring!

Burner installation

The factory supplied forced air-
burner is mounted on the front
of the appliance with a clamping
flange.
The following must be observed:

Only type-tested hot air heat-

type-tested hot air heat-

ers with forced-air oil burners
complying with DIN EN 267 or
forced-air gas burners (comp-
lying with DIN EN 676) may be
used.

Power limitation for single-

stage burner operation (up to
70 kW) is not required for hot
air heaters.

AttENtION

Installation, adjustment and
maintenance of the gas supply
must only be carried out by
specialists authorised by GVU!