beautypg.com

Remko vrs, Accessories – REMKO VRS Series User Manual

Page 32

background image

32

REMKO VRS

Appliance
type dim.

in mm

VRS

25

VRS

50

VRS

75

VRS

100

VRS

130

VRS

170

VRS

200

VRS

270

VRS

340

VRS

440

VRS

540

A

(vertical)

670 870 870 970 1070 1270 1270 1430 1430

--

--

A1

(horizontal)

970 1120 1430 1430 1780 2010 2010 2800 2800

--

--

B

(vertical)

820 1020 1020 1120 1220 1380 1380 2010 2010

--

--

B1

(horizontal)

1120 1320 1600 1600 2010 2200 2200 2200 2200

--

--

C

45

50

D

55

80

120

Wall bracket type KN

U-profile construction for mounting vertical or horizontal units
on walls with a minimum thickness of 24 cm (structural calculation
required).
Recommended is the use of continuous M 16 steel reinforced threaded
bolts (local mounting material)

Flexible pipe type SG

Flexible connection (vibration isolation) between unit and air duct system.
Mounting option Pos. I, II, III, IV or also combined.

Dim. in

mm

VRS

25

VRS

50

VRS

75

VRS

100

VRS

130

VRS

170

VRS

200

VRS

270

VRS

340

VRS

440

VRS

540

D

790

940 1190 1190 1465 1590 1590 1170 1170 1620 1620

E

540

740

740

840

945 1130 1130 1570 1570 2155 2155

G

485

485

485

485

545

630

630

695

695 1060 1060

K

465

670

670

765

895 1085 1085 1170 1170 1620 1620

Z

30

30

30

30

30

30

30

30

30

35

35

Dimensions in brackets only for air outlet and
direct duct connection to air inlet Pos. IV

A (A1)

D

C

B (B1)

max. 150

G(E)

Z

Z

K(D)

We reserve the right to make dimensional and design changes in the interest of technical advances.

Accessories

Dust filter type F

for free air intake

Plate filter consists of 2 grille frames with intermediate,
easy to replace filter mats with the filter class G3.

Further filter classes are available on request.

1 set dust filters F always consists of air inlet Pos. I + II + III..

Tech-

nical

data

VRS

25

VRS

50

VRS

75

VRS

100

VRS

130

VRS

170

VRS

200

VRS

270

VRS

340

VRS

440

VRS

540

F m

2

0.79 1.02 1.24 1.28 1.18 1.70 1.70 2.46 2.46 5.15 5.15

A m/s

0.6

0.9

1.2

1.5

2.1

1.6

2.0

2.2

2.3

2.5

2.9

F m

2

= Filter area in m

2

A m/s = Flow in m/s
Initial pressure loss about 100 Pa at standard pressure.
With a change of filter class, the changed pressure loss must be taken into account!

Pos. I

Pos. III

Pos. II