Remko vrs, Accessories – REMKO VRS Series User Manual
Page 32
![background image](https://www.manualsdir.com/files/802235/content/doc032.png)
32
REMKO VRS
Appliance
type dim.
in mm
VRS
25
VRS
50
VRS
75
VRS
100
VRS
130
VRS
170
VRS
200
VRS
270
VRS
340
VRS
440
VRS
540
A
(vertical)
670 870 870 970 1070 1270 1270 1430 1430
--
--
A1
(horizontal)
970 1120 1430 1430 1780 2010 2010 2800 2800
--
--
B
(vertical)
820 1020 1020 1120 1220 1380 1380 2010 2010
--
--
B1
(horizontal)
1120 1320 1600 1600 2010 2200 2200 2200 2200
--
--
C
45
50
D
55
80
120
Wall bracket type KN
U-profile construction for mounting vertical or horizontal units
on walls with a minimum thickness of 24 cm (structural calculation
required).
Recommended is the use of continuous M 16 steel reinforced threaded
bolts (local mounting material)
Flexible pipe type SG
Flexible connection (vibration isolation) between unit and air duct system.
Mounting option Pos. I, II, III, IV or also combined.
Dim. in
mm
VRS
25
VRS
50
VRS
75
VRS
100
VRS
130
VRS
170
VRS
200
VRS
270
VRS
340
VRS
440
VRS
540
D
790
940 1190 1190 1465 1590 1590 1170 1170 1620 1620
E
540
740
740
840
945 1130 1130 1570 1570 2155 2155
G
485
485
485
485
545
630
630
695
695 1060 1060
K
465
670
670
765
895 1085 1085 1170 1170 1620 1620
Z
30
30
30
30
30
30
30
30
30
35
35
Dimensions in brackets only for air outlet and
direct duct connection to air inlet Pos. IV
A (A1)
D
C
B (B1)
max. 150
G(E)
Z
Z
K(D)
We reserve the right to make dimensional and design changes in the interest of technical advances.
Accessories
Dust filter type F
for free air intake
Plate filter consists of 2 grille frames with intermediate,
easy to replace filter mats with the filter class G3.
Further filter classes are available on request.
1 set dust filters F always consists of air inlet Pos. I + II + III..
Tech-
nical
data
VRS
25
VRS
50
VRS
75
VRS
100
VRS
130
VRS
170
VRS
200
VRS
270
VRS
340
VRS
440
VRS
540
F m
2
0.79 1.02 1.24 1.28 1.18 1.70 1.70 2.46 2.46 5.15 5.15
A m/s
0.6
0.9
1.2
1.5
2.1
1.6
2.0
2.2
2.3
2.5
2.9
F m
2
= Filter area in m
2
A m/s = Flow in m/s
Initial pressure loss about 100 Pa at standard pressure.
With a change of filter class, the changed pressure loss must be taken into account!
➠
➠
➠
Pos. I
Pos. III
Pos. II