REMKO VRS

For installation of the heating
appliances, the requirements
and regulations applicable in the
respective federal state must be
observed.

The following must also be
observed:

The heating appliances must be

securely installed.

The heating appliances must

be floor-mounted securely
and stress-free, preferably on
a separate vibration damped
base.

It must be ensured that the

fan output (nominal pressure)
corresponds to the respective
air-sided resistances.
Measure rated current!

The air inlets and outlets must

be kept free.

A suffi cient supply of combus-

A sufficient supply of combus-
tion air must be ensured.

In the event that excess or low

pressure or high air contamina-
tion should occur in the instal-
lation room, a separate burner
fresh air intake unit (accessory)
must be installed.

Where high air contamination

is expected in the installation
room, the circulated air should
be drawn in via appropriate
filters (accessory).
The resistance on the air inlet
side should be noted and the
fan power adjusted accor-
dingly!

Room thermostat connection

The room thermostat (accessory)
must be mounted at a position
which is easy to access for tem-
perature control.

The thermostat sensor may not be
located directly in the hot/cold air
stream and should not be mounted
directly on a cold
surface.

The procedure is the same for the
installation of an automatic day/
night temperature control or other
temperature controls available as
accessories.

230V type heaters

The connection of a room thermo-
stat or a day/night temperature
control for 230V types takes place
in the control box at the ther-
mostat plug socket provided as
standard.

Connection must be carried out as
follows:

Disconnect the existing shunt plug
and connect thermostat plug 2 to
thermostat plug socket 1 on the
control box.

Thermostat plugs are available as
an accessory (EDP No. 1101020)
for control units supplied without
these standard plugs.

Installation and assembly

2

1

Chimney connection

Connection must comply with DIN
18160, part 1 and the dimensions
with DIN 4705, part 1.

Correct chimney duct installati-

on must be ensured.

The chimney connection must

be connected correctly and in
compliance with the applicable
regulations.

The chimney connection

must only be connected to a
previously approved chimney
system.

Electrical connection

Electrical connection of the heating
appliance must be carried out by
authorised specialists as defined in
DIN EN 60335-1 and VDE 0116.

An emergency switch must be

provided at an easily accessible
point for heaters with a nominal
heat output above 50 kW.

The emergency switch must be

protected against unauthorised
use.

AttENtION

Die Transportpalette bzw.
die The transport pallet and
timbers must be removed
prior to installation.

NOtE

Air intake must only take place
via the air intake openings
provided.
If the heater does not have an
air intake at the bottom, this
must be sealed to prevent the
intake of extraneous air.

NOtE

All electrical wiring terminals
must be checked for tightness
and retightened if necessary.