Cleaning the combustion
chamber and heat exchanger

1. Disconnect the appliance from

the mains supply.

2. Shut off the fuel supply.

Remove the following
components:

1. The forced-air burner.

2. Burner plate

with burner

flange.

3. Front

lining plate(s).

4. One side

lining plate (left or

right depending on structural
conditions).

5. The two front

inspection

covers.

6. The side

inspection cover.

7. Remove the flue gas brakes

from the heat exchanger

tubes and clean or replace if
damaged.
The correct assignment of
the exchanger tubes must be
ensured!

8. Clean the heat exchanger

tubes

with suitable cleaning

agents to remove adhering
combustion residues.

9. Remove the combustion resi-

dues from the front and rear
collection boxes

with a

suitable vacuum cleaner.

Fig. VRS 50 vertical
without burner

10. The combustion residues in the

combustion chamber must be
removed though the burner
opening also using a suitable
vacuum cleaner.

A special boiler cleaning set
for the REMKO industrial
vacuum cleaner is available as
an accessory.

11. After cleaning, all parts must

be carefully refitted in reverse
order.

12. The correct assignment of the

exchanger tubes and correct
seating of all seals must be
ensured.

Damaged or deformed seals
must be replaced.

13. Burner maintenance must be

carried out as specified in the
separate operating instructions
of the burner.

3

5

6

1

2

4

7

8

8

AttENtION

It does not suffice to switch off
the unit only via the switch!

NOtE

The limitation of exhaust fume
losses must be maintained in
accordance with §11 of the
Ordinance on Small Firing
Installations (1st BImSchV).

AttENtION

The burner and all control
units must be checked for per-
fect functioning.