Installation requirements – REMKO CLK 30 User Manual
Page 5
5
Monitoring operation of device
All functions of the unit are fully automatic and moni-
tored for safety by the safety facility and the automatic
burner relay (part of the forced-air burner).
If the flame burns irregularly or goes out, the unit is
switched off by the automatic burner relay. The control
lamp on the control panel and the malfunction lamp of
the automatic burner relay light up.
Before the unit can be restarted, the automatic burner relay
must be released by pressing the external reset button on
the operating panel or the reset button on the automatic
burner relay.
The fan control (TR) regulates operation of the fan. The
temperature monitor (TW) limits or regulates the tem-
perature of the unit in heating mode.
The safety temperature limiter (STB) interrupts heating
mode when extreme overheating occurs or if the tem-
perature monitor (TW) stops working or is defective.
The STB can only be manually released after the unit
has cooled down.
G
Before the STB is released to begin operation
again, the reason the STB was activated must be
determined.
Installation Requirements
The heaters may only be installed in compliance with
the relevant regulations, in particular, regulations gov-
erning the installation and operation of fireplaces and
furnaces.
Any national/regional emission control laws or regula-
tions must also be observed.
à Avoid under- or overpressure in the room where the
unit is installed, as this would result in combustion
troubles.
à Make absolutely sure that the opening for air intake
and output is adjusted to the fan power (see model
plate).
If this is not possible, the burner has to be equipped
with a separate air supply device to ensure optimum
combustion.
Installation in closed, well aerated rooms without
connection to a chimney
à The units may only be operated when the minimum
amount of air required for combustion is supplied.
à A safe exhaustion of the waste gases is to be en-
sured to exclude inadmissible pollution.
- Fresh air is supplied from below.
- Waste gases are expelled upwards.
Outside installation
à Operation of the unit may not have any harmful ef-
fects or cause any unreasonable problems.
à The unit operator must ensure that unauthorised per-
sons are prevented from manipulating the unit or its
power supply.
à Because rain and snow can be sucked in by the air
supply fan, a suitable protective covering should be
used.
Heating Rooms
à Warm air generators may only be operated with a
room thermostat when heating rooms.
Accessories.
à Make sure that there is enough fresh air to ensure
optimum combustion.
Safety zones
à To ensure safe operation and guarantee unhindered
access to the unit for maintenance work, a safety
zone of 1.5 m should be maintained around the unit.
à Floors and ceilings must be fire-resistant.
Electrical Connection
à The units are operated with 400 V / 3~N / 50 Hz.
à The unit must be connected to the power source at a
special terminal equipped with a switch to protect
against faulty currents.
à Extension cable may only be laid by authorised elec-
tricians based on the capacity of a unit, the length of
the cable and in accordance with local requirements.
à All extension cable may only be used once they have
been unrolled.
G
While the unit is in operation, the safety features
may not be bypassed or blocked!