Technical data – REMKO CLK 30 User Manual
Page 12
12
Technical Data
Model
CLK 30
CLK 50
CLK 70
CLK 120
CLK 150
rated heat power max.
kW
29
46
68
121
144
rated heat output
kW
26.5
42
62
110
131
rated air output
1)
m³/h
1,760
2,780
4,920
7,350
8,920
pressure,
max. complete
Pa
90
145
185
220
260
fuel
heating oil or diesel (DIN 51603)
fuel consumption, max.
L/h
2.85
4.5
6.6
11.8
14.0
oil nozzle (Danfoss)
2)
USG 0.6 / 60°S 1.00 / 60°S 1.35 / 60°S 2.25 / 80°S 2.75 / 80°S
pump pressure, approx.
2)
bar
11.0
11.0
12.0
13.0
13.0
waste gas emissions, max.
%
9
waste gas volume, approx.
kg/h
48
75
115
195
230
furnace resistance, approx. (start/operation)
Pa
145 / 40
150 / 45
180 / 80
400 / 90
480 / 120
required chimney draught
Pa
0
electrical connection
V/Hz
1~ 230/50
power consumption max. (total unit)
W
370
420
860
1,300
1,900
rated current max. (total unit)
A
1.8
2.0
4.0
6.0
8.8
power consumption max. (fan)
W
150
200
610
900
1,500
rated current max. (fan)
A
0.7
0.9
2.8
4.3
6.5
capacitor (fan)
µF
3
5
14
16
30
power consumption
(
oil preheater
)
W
—
—
—
30
30
fuse protection (supplied)
A
10
10
10
16
16
increase of temperature (
∆
t
)
K
45
52
44
52
52
sound pressure level L
pA
1m
3)
dB (A)
62
66
70
74
78
air outlet Ø
mm
300
300
400
500
500
waste gas connection Ø
mm
150
150
150
200
200
dimensions: length, total
mm
1,450
1,450
1,610
2,100
2,100
width, total
mm
660
660
730
920
920
height, total
mm
1,000
1,000
1,120
1,350
1,350
weight without burner
kg
112
118
158
282
291
weight with burner
kg
126
132
172
303
312
1)
∆
t
45K / 1.2 kg/m³
2) The mentioned nozzle-sizes and pump pressures were determined on the basis of adjustment tests on test units. The oil throughput had been
measured out. The specifications serve only as guidelines due to product-specific differences in nozzle and pressure tolerances and oil temperature.
3) Noise measuring without burner.
We reserve the right to make changes to dimensions and design in the interest of technical progress.