Page 22

background image

Condensation connection - outdoor component

Opening for

condensation

connection

Condensation pan of

outdoor component

Condensation connection

All electrical installation

work should be performed

by specialist contractors.

Isolate the voltage supply

when connecting the electrical

terminals.

CAUTION

Electrical connection

Mains cable must be installed as
voltage supply to the indoor unit
and a control cable to the outdoor
component, with appropriate
safeguards.

Condensation connection

Due to the dew point shortfall,
condensation forms on the
vaporiser during the cooling
operation

and on the liquefier

during heating operation.

Below the vaporiser is a collection
tray, which must be connected to
a drain.
The lower part of the outdoor
component housing is formed in
the shape of a collection tray. The
condensate connection included
in the scope of delivery is to be
attached here.

The condensation pipe should
have a fall of min. 2 %. (Fig.
10)

. If necessary, fit vapour

diffusion tight insulation.

The condensation pipe from
the unit should run freely
into the drainage pipe. If the
condensation runs directly
into a sewer pipe, fit a trap to
prevent any unpleasant odours.

The condensation hose is designed
to be installed on the left side
(view from front).

10

Fall of condensation pipe

minimum
2% fall

When operating the unit at
ambient temperatures below
0 °C , make sure to route the
condensation pipe freeze proof.
The lower part of the housing
is also to be kept frost free by
the customer, in order to ensure
permanent draining of the
condensate.
If necessary, fit supplementary
pipe heating.

After completed routing, check
for unobstructed condensation
discharge and ensure that a
permanent seal is provided.

Connecting the indoor unit

We recommend installing
a master / repair switch on the
building near the indoor unit.

Voltage is supplied to the
indoor unit, the outdoor
component is supplied through
the control cable from the
indoor unit to the outdoor
component.

The terminal blocks for making
the connections are located on
the front of the unit. When the
unit is installed, measurements
can be made from the front by
removing the cover.

The device's scope of delivery
includes a five metre long, four-
core control cable for connecting
the indoor unit to the outdoor
component. The control cable to
the outdoor component contains
a data cable which serves to
realise communication between
the indoor unit and the outdoor
component. This is used for
controlling the cooling and heating
performance and for forwarding
fault indications to the indoor unit.

REMKO RVT...DC

22