Mounting points for wall bracket

RVT 261DC IT

RVT 351DC IT

RVT 521DC IT

All dimensions in mm

1000

50

298

65

65

50

750

250

65

65

45

815

270

65

65

45

Connection variations

1 Outlet on the wall, right
2 Outlet through the wall, right
3 Outlet through the wall, left
4 Outlet on the wall, left

1

2

3

4

Connection variations of
indoor unit

Unit installation

The indoor unit is attached by
means of a wall bracket, under
consideration of air discharge side
located in the lower part.

1. Mark the mounting points

on the statically permissible
building sections according to
the dimensions of the unit.

2. If necessary, remove the break

out opening on the housing.

3. Connect the refrigerant

pipes, electrical cables and
condensation pipe to the indoor
unit as described below.

4. Hang the indoor unit onto the

wall bracket by tilting it back
slightly and by pressing the
bottom part of the unit against
the bracket (Figure 5).

5. Check that the unit is level.

Wall bracket
for indoor unit

The wall bracket for the unit must
be attached with suitable screws
and anchors.

Installation

Installation should only be
performed by authorised
specialists.

NOTE

Oil return measures

If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed
for every 2.5 metres of height
difference.

5 Hooking in

Oil return measures

Outdoor

component

Oil pump bend

in suction pipe to

outdoor component

1 x every 2.5

metres of rising pipe

Radius:

min. 50 mm

max. 15 m

Indoor unit