Installation – REMKO RVT 261 DC User Manual
Page 19
Mounting points for wall bracket
RVT 261DC IT
RVT 351DC IT
RVT 521DC IT
All dimensions in mm
1000
50
298
65
65
50
750
250
65
65
45
815
270
65
65
45
Connection variations
1 Outlet on the wall, right
2 Outlet through the wall, right
3 Outlet through the wall, left
4 Outlet on the wall, left
1
2
3
4
Connection variations of
indoor unit
Unit installation
The indoor unit is attached by
means of a wall bracket, under
consideration of air discharge side
located in the lower part.
1. Mark the mounting points
on the statically permissible
building sections according to
the dimensions of the unit.
2. If necessary, remove the break
out opening on the housing.
3. Connect the refrigerant
pipes, electrical cables and
condensation pipe to the indoor
unit as described below.
4. Hang the indoor unit onto the
wall bracket by tilting it back
slightly and by pressing the
bottom part of the unit against
the bracket (Figure 5).
5. Check that the unit is level.
Wall bracket
for indoor unit
The wall bracket for the unit must
be attached with suitable screws
and anchors.
Installation
Installation should only be
performed by authorised
specialists.
NOTE
Oil return measures
If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed
for every 2.5 metres of height
difference.
5 Hooking in
Oil return measures
Outdoor
component
Oil pump bend
in suction pipe to
outdoor component
1 x every 2.5
metres of rising pipe
Radius:
min. 50 mm
max. 15 m
Indoor unit
19