background image

Fault indication by flashing code

REMKO MXD

18

LED

Operation

LED

Timer

LED

Defrost

LED

Alarm

OU dis-

play

Cause

Required action

flashes

-

Sensor air circulation faulty / tripped

Check resistance

flashes

-

Sensor on vaporiser faulty / tripped

Check resistance

flashes

E7

Communication error between PCBs
OU & IU

Check electrical connection
leads

flashes

flashes

E0

EEPROM error

Check EEPROM

flashes

On

-

Inverter module shutdown

flashes

-

Condensation pump float switch faulty/
tripped

Contact specialist dealer

flashes

On

E4

Outdoor temp sensor on OU tripped

Check resistance and tem-
perature on sensor

flashes

On

On

E5

Surge voltage on outdoor unit

Check power supply

flashes

On

P0

Excess temperature in compressor

Allow compressor to cool

flashes

On

On

-

Mode conflict

Switch system off

flashes

flashes

flashes

P3

OU power consumption too high

Check power consumption

This manual is related to the following products: