Keys
Cooling mode
Automatic mode
MODE key
Use the MODE key to select between individual operating modes. A total
of 5 modes are available:
Using the key, the target temperature can be adjusted up or down by
1°C. The temperature range lies between 17°C and 30°C
1. Automatic
cooling or heating operation
2. Cooling
primarily summer mode
3. Dehumidifying operating mode for summer or winter
4. Heating
primarily winter mode
5. Circulation
air circulation only
MODE
MODE
MODE
Automatic
Cooling
Dehumidifying
Heating
Air circulation
▼
▲
▼
▲
In automatic mode, the controller autonomously selects between heating,
circulation or cooling mode based on the room temperature Tr and
the selected target value Ts. The target value can be adjusted between
17°C and 30°C by means of the
▲/▼ keys. The fan speed is selected
automatically.
AUTOMATIC MODE
AUTOMATIC
MODE
Operational sequence:
If Tr is less than 1K as Ts, then operating mode "Heating" is selected.
If Tr is greater than 2K as Ts, then operating mode "Cooling" is selected.
If Tr is between Ts -1K as Ts +2K, then operating mode "Circulation" is selected.
If after the compressor is shut down and not required for more than 15 mins. within an operating mode, then,
in the event that the room temperature deviates, the corresponding mode heating, cooling or circulation
will be selected again.