3 sound pressure level – REMKO RVT 263 DC User Manual
Page 11
2.3 Sound pressure level
1m
1m
5m
10m
1m
5m
10m
Fig. 3: Distance-dependent sound pressure level for the outdoor unit in relation to installation type, in accord-
ance with the drawing
Distance-dependent sound pressure level *)
Unit type
Sound power max.
[dB(A)]
Installation type, in
accordance with the
drawing
1m
[dB(A)]
5m
[dB(A)]
10m
[dB(A)]
15m
[dB(A)]
RVT 263 DC
59
In free field
51,0
37,0
31,0
27,5
In front of a wall
54,0
40,0
34,0
30,5
RVT 353 DC
63
In free field
55,0
41,0
35,0
31,5
In front of a wall
58,0
44,0
38,0
34,5
RVT 523 DC
61
In free field
53,0
39,0
33,0
29,5
In front of a wall
56,0
42,0
36,0
32,5
RVT 683 DC
67
In free field
59,0
45,0
39,0
35,5
In front of a wall
62,0
48,0
42,0
38,5
*) All information without guarantee. Exact sound values must be determined by an expert!