beautypg.com

2 technical data, 1 unit data, Technical data 2.1 unit data – REMKO MXW 202 User Manual

Page 7: Technical data, Unit data

background image

2

Technical data

2.1

Unit data

Series

MXW 202

MXW 262

MXW 352

MXW 522

Operating mode

Wall unit for inverter multisplit outdoor units for cooling and heating

Nominal cooling output

1)

kW

2.05

2.64

3.51

4.98

Nominal heat capacity

2)

kW

2.34

2.93

3.81

5.27

Approx. application area

(room volume)

m

3

60

80

110

160

Adjustment range,

room temperature

°C

+17 to +30

Operating range

°C

+17 to +32

Refrigerant

R 410A

4)

Max. operating pressure

kPa

4200/1500

Air flow volume per level

m³/h

350/460/530

350/460/530

430/540/630

650/780/1000

Sound pressure level per
stage

3)

dB (A)

28/37/40

28/37/40

31/38/42

34/40/47

Sound power

dB (A)

52

52

54

56

Power supply

V/Hz

230 / 1~ / 50

Enclosure class

IP

X 0

Electrical rated power con-
sumption, cooling

1)

W

24

24

24

62

Electrical rated power con-
sumption, heating

2)

W

24

24

24

62

Electrical rated current con-
sumption, cooling

1)

A

0.11

0.11

0.11

0.28

Electrical rated current con-
sumption, heating

2)

A

0.11

0.11

0.11

0.28

Refrigerant connection

Liquid line

Inche

s

(mm)

1/4 (6.35)

1/4 (6.35)

1/4 (6.35)

1/4 (6.35)

Refrigerant connection

Suction pipe

Inche

s

(mm)

3/8 (9.52)

3/8 (9.52)

3/8 (9.52)

1/2 (12.70)

Condensate drainage con-

nection

mm

18

18

18

18

7

This manual is related to the following products: