Installation instructions for qualified personnel, Remko mxw – REMKO MXW 202 User Manual
Page 20
"RESET" key
This indented key can be used to reset the remote
control.
RESET
Fig. 23: "Reset" key
5
Installation instructions
for qualified personnel
Important notes prior to installation
Observe the operating manuals for the indoor unit
and the outdoor unit when installing the entire
system.
n
Transport the unit in its original packaging as
close as possible to the installation location.
You avoid transport damage by doing so.
n
Check the contents of the packaging for com-
pleteness and check the unit for visible trans-
port damage. Report any damage immediately
to your contractual partner and the shipping
company.
n
Lift the unit on the corners and not on the
refrigerant or condensate drainage connec-
tions.
n
The refrigerant piping (injection and suction
pipe), valves and connections must be insu-
lated against vapour density. If necessary also
insulate the condensate drainage line.
n
Select an installation location which allows air
to freely flow through the air inlet and outlet
(see section "Minimum clearances")
n
Do not install the unit in the immediate vicinity
of devices which generate intensive thermal
radiation. Installation in the vicinity of thermal
radiation reduces the unit output.
n
Install the refrigerant piping from the indoor unit
to the outdoor unit.
n
Seal off open refrigerant piping with suitable
caps or adhesive strips to prevent the infiltra-
tion of moisture and never kink or compress
the refrigerant piping.
n
Only use the union nuts supplied with the
refrigerant piping. These should only be
removed shortly before connecting the refrig-
erant piping.
n
Carry out all electrical wiring in accordance
with applicable DIN and VDE standards.
n
Ensure the electrical cables are properly con-
nected to the terminals. Otherwise there is a
risk of fire.
Installation materials
The indoor unit is attached to the wall by a wall
bracket and 4 screws (to be provided by the cus-
tomer).
Selection of installation location
The indoor unit is designed for horizontal wall
installation above doors. However, it can also be
used in the upper wall area (min. 1.75 m above the
floor).
REMKO MXW
20