Fig. 30

Fig. 31

2 -

Elbow bend

3 -

Elbow bend

4 -

Flue extension

6 -

Straight header

7 -

Roof fl ashing

23

Cut a 105 mm diameter hole through the ceiling
and/or roof, at the point previously marked.

Fit a roof flashing sleeve (fig. 31 item 7) to the roof,
available from Ravenheat Manufacturing.

Insert the Vertical Flue terminal assembly through
the flashing plate from the outside.

Fix the appliance to the wall, locating onto the
hanging bracket.

Measure the vertical distance between the top of
the flue (Fig. 29) and the bottom of the flue terminal
assembly (Fig. 28). The measurements should be
taken from the outer diameter of the flue.
NOTE: Where this length does not match any
standard combination of the extensions, they can
be cut to the required length (Fig. 30).

When cutting both inner and outer ducts of the
extension, always cut on spigot side, and they must
be de-burred.

5.8 REASSEMBLE

BOILER

AS

PER

(sect.

5.6).

5.8.1

Fitting valve pack

Remove plastic caps from boiler connection
and fit valves as per fig. 32 using washers
provided.

5.9 GAS

CONNECTION

(fig.

32).

5.9.1

A minimum working gas pressure of 20 mbar
(8 in w.g.) must be available at the boiler inlet
at full flow rate (37 mbar for propane, 29 mbar
for butane).

5.9.2

Fit gas service cock to the boiler via the union
nut and connect gas pipe. Do not overtighten
and use another spanner as a counter force to
avoid straining internal connections.
Important consult (sect 4.5.1).

5.10

CENTRAL HEATING CONNECTION

(fig.

32).

5.10.1 Before any central heating connections are

made to the boiler all system valves should

be opened and the system thoroughly flushed

out with cold water.

- Connect the central heating return pipe

to the isolating cock.

- Connect the central heating flow pipe to

the isolating cock marked CHF.

- Pipe dimensions and positions are

marked on template supplied.

5.11

DOMESTIC HOT WATER (fig. 32)

5.11.1

The domestic hot water circuit does not need
a safety valve but it is essential to ensure that
the pressure of the cold water supply does
not exceed 10 bar. If in doubt it is advisable
to install a pressure reducing valve. The
minimum pressure needed to operate the
domestic hot water system is 0.5 bar with a
flow of approx 3 Its per min.

- Connect the 15 mm. cold water pipe to the

stop cock to the appliance inlet.

- Connect the 15 mm. hot water pipe with a

suitable connection.