9

Table 1 - Minimum Room Volume, Indoor Air Only*

Input Mbh

Standard

Method

Known Air Infiltration Rate Method (Air Changes Per Hour)

0.1

0.2

0.3

0.4

0.5

0.6

45

2250

9450

4725

3150

2363

1890

1575

70

3500

14700

7350

4900

3675

2940

2450

96

4800

20160

10080

6720

5040

4032

3360

120

6000

25200

12600

8400

6300

5040

4200

145

7250

30450

15225

10150

7613

6090

5075

170

8500

35700

17850

11900

8925

7140

5950

195

9750

40950

20475

13650

10238

8190

6825

245

12250

51450

25725

17150

12863

10290

8575

295

14750

61950

30975

20650

15488

12390

10325

* Table values based on boiler only. Add volume for any additional appliances.

4 - VENTILATION & COMBUSTION AIR

Provide combustion air and ventilation air in accordance

with the section “Air for Combustion and Ventilation,” of the

National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections

8.2, 8.3 or 8.4 of Natural Gas and Propane Installation

Code, CAN/CSA B149.1, or applicable provisions of local

building codes.

Provide make-up air where exhaust fans, clothes dryers,

and kitchen ventilation equipment interfere with proper

operation.

National Fuel Gas Code recognizes several methods

of obtaining adequate ventilation and combustion air.

Requirements of the authority having jurisdiction may

override these methods.

• Engineered Installations. Must be approved by

authority having jurisdictions.

• Mechanical Air Supply. Provide minimum of 0.35

cfm per Mbh for all appliances located within space.

Additional requirements where exhaust fans installed.

Interlock each appliance to mechanical air supply

system to prevent main burner operation when

mechanical air supply system not operating.

• All Indoor Air. Calculate minimum volume for all

appliances in space. Use a different method if

minimum volume not available.

о Standard Method. Cannot be used if known air

infiltration rate is less than 0.40 air changes per

hour. See Table 3 for space with boiler only. Use

equation for multiple appliances.
Volume ≥ 50 ft

3

x Total Input [Mbh]

о Known Air Infiltration Rate. See Table 3 for

space with boiler only. Use equation for multiple

appliances. Do not use an air infiltration rate

(ACH) greater than 0.60.
Volume ≥ 21 ft

3

/ACH x Total Input [Mbh]

о Refer to National Fuel Gas Code for opening

requirements between connection indoor spaces.

• All Outdoor Air. Provide permanent opening(s)

communicating directly or by ducts with outdoors.

о Two Permanent Opening Method. Provide opening

commencing within 12 inches of top and second

opening commencing within 12 inches of bottom

enclosure.

ƒ

Direct communication with outdoors or

communicating through vertical ducts. Provide

minimum free area of 1 in

2

per 4 Mbh of total

input rating of all appliances in enclosure.

ƒ

Communicating through horizontal ducts.

Provide minimum free area of 1 in

2

per 2

Mbh of total input rating of all appliances in

enclosure.

о One Permanent Opening Method. Provide opening

commencing within 12 inches of top of enclosure.

Provide minimum clearance of 1 inch on sides

and back and 6 inches on front of boiler (does not

supersede clearance to combustible materials).

о Combination Indoor and Outdoor Air. Refer to

National Fuel Gas Code for additional requirements

for louvers, grilles, screens and air ducts.

• Combination Indoor and Outdoor Air. Refer to

National Fuel Gas Code for application information.

National Gas and Propane Installation Code Requires

providing air supply in accordance with:

• Section 8.2 and 8.3 when combination of appliances

has a total input of up to and including 400 Mbh (120

kW).

• Section 8.4 when combination of appliances has total

input exceeding 400 Mbh (120 kW).

• Refer to Natural Gas and Propane Installation Code

for specific air supply requirements for enclosure

or structure where boiler is installed, including air

supply openings and ducts.