beautypg.com

Warning – Pennco 15B045FE User Manual

Page 11

background image

11

Hydronic Piping - General

• Install piping in accordance with authority having

jurisdiction.

• Support system piping and safety relief valve discharge

piping.

Special Conditions

• System piping exposed to freezing conditions: Use

inhibited proplyene glycol solutions certified by fluid

manufacturer for use with closed water heating system.

Do not use automotive or ethylene glycol.

• Boiler installed above radiation level (or as required by

authority having jurisdiction). Install low water cutoff.

• Boiler used in connection with refrigeration system.

Install piping in parallel with boiler, with appropriate

valves to prevent chilled medium from entering boiler.

See Figure 2, Page 10.

• System piping connected to heating coils located in air

handling unit exposed to refrigerated air circulation.

Install flow control valves or other automatic means to

prevent gravity circulation of boiler water during cooling

cycle.

Safety Relief Valve

WARNING

Burn and scald hazard. Safety relief valve could

discharge steam or hot water during operation.

Install discharge piping per these instructions.

!

NOTICE

Boiler rated at 100 psig maximum allowable working

pressure. Boiler provided with 30 psig safety relief

valve. Field source safety relief valve for system

pressures greater than 30 psig. Temperature-

pressure gauge provided with boiler is satisfactory

for 30-50 psig operation. Replace temperature-

pressure gauge for system pressure over 50 psig.

Scale on dial must be graduated to not less than 1½

nor more than 3½ time safety relief valve pressure

settings.

• Do not install shutoff valve between boiler and safety

relief valve.

• Systems with automatic fill valves require back flow

prevention device.

• Install discharge piping from safety relief valve. See

Warning, Page 8.

• When boiler is connected to heating system utilizing

multiple zoned circulators, each circulator must be

supplied with flow control valve to prevent gravity

circulation.

• Hot water boilers and system must be filled with water

and maintained to minimum pressure of 12 psi.

• Bypass piping is an option which gives ability to adjust

the supply boiler water temperature to fit the system or

condition of installation. This method of piping, however,

is not typically required for baseboard heating systems.

Typical installations where bypass piping is used are as

follows:

A. This method is used to protect boilers from

condensation forming due to low temperature

return water. Generally noticed in large converted

gravity systems or other large water volume

systems. Figures 3 & 4, Page 11.

B. These methods are used to protect systems using

radiant panels and the material they are encased

in from high temperature supply water from the

boiler and protect boiler from condensation.

NOTE#1: When using bypass piping, adjust valves V1 & V2

until desired system temperature is obtained.
NOTE#2: Bypass loop must be same size piping as the

supply and return piping.

• Installation using circulators and zone valves are shown

in Figures 3-8 . For further piping information refer to

AHRI Installation and Piping Guide.

• For zone controls and indirect hot water, refer to

appropriate manufacturer instructions.

• For Low Water Cutoff, see Dimensions page 5 for

minimum height. Use kit number 550009885.

Follow

instructions enclosed with the kit.

• For other LWCO's follow their specific manufacturer

instructions.

5 - CONNECTING SUPPLY & RETURN PIPING

This manual is related to the following products: