APPENDIX A - CONTROL MODULE

A.6 Boiler High Limit Temperature Controller

• When water temperature reaches setpoint, controller

ends heating cycle.

• When water temperature drops below setpoint minus

differential, controller restarts heat cycle to re-heat

boiler water.

• If water temperature exceeds maximum allowed

temperature (220°F or 104°C), controller enters manual

reset lockout state.

• For manual reset press any onboard button or cycle

power to reset.

Figure 21

- Basic Control Algorithm Example

A.7 Troubleshooting

• Following service procedures are provided as general

guide.

• On lockout and retry models, meter readings between

gas control and ignition module must be taken within

trial for ignition period. Once ignition module shuts

off, lockout models must be reset through key buttons

and display. On retry models, wait for retry or reset at

thermostat.

• Check for correct installation and wiring before replacing

any component.

• Control module cannot be repaired. If it malfunctions, it

must be replaced.

• Use only qualified service agent to service ignition

systems.

1.

Perform checkout as first step in troubleshooting.

2.

Check troubleshooting guide to pinpoint cause of

problem. See Table 5, page 35.

3.

If troubleshooting indicates ignition problem, see

Ignition System Checks to isolate and correct the

problem.

4.

Perform checkout procedure following troubleshooting

guide again to verify system is operating normally.

A.8 Troubleshooting Error Codes

Integrated boiler control uses advanced diagnostic

capability to assist in troubleshooting error conditions.
Table 5 shows codes that could arise on integrated display

during fault.
Suggestions are provided in Table 5 for servicing these

potential errors.