• Make visual inspection of main burner and pilot flames

at start of heating season and again in mid-season. Main

burner flame should have well defined inner blue mantel

with lighter blue outer mantel. Check burner throats and

burner orifices for lint or dust obstruction. See Figure 16.

• Pilot flame should envelop ⅜ to ½ inch of tip of ignition/

sensing electrode. See Figure 18.

• To adjust pilot flame, remove pilot adjustment cover

screw and turn inner adjustment screw counterclockwise

to increase or clockwise

to decrease pilot

flame. Be sure to replace cover screw after adjustment to

prevent possible gas leakage. See Figure 14, Page 20.

• Check burners and pilot for signs of corrosion, rust or

scale buildup. Area around boiler must be kept clear

and free of combustible materials, gasoline and other

flammable vapors and liquids.

• Free flow of combustion and ventilating air to boiler and

boiler room must not be restricted or blocked.

• Inspect field sourced low water cutoffs annually, or

as recommended by low water cutoff manufacturer.

Flush float type low water cutoffs per manufacturer's

instructions.

• Employ a qualified service agency to make annual

inspection of boiler and heating system. They are

experienced in making the inspections outlined above,

and, in event repairs or corrections are necessary,

trained technicians make the proper changes for safe

operation of the boiler.