beautypg.com

Warning – Pennco 15B045FE User Manual

Page 16

background image

16

When existing boiler is removed from a common venting

system, the system is likely to be too large for the proper

venting of the appliances still connected to it.
Removal Of Boiler From Venting System
At the time of removal of an existing boiler, the following

steps shall be followed with each appliance remaining

connected to the common venting system placed in

operation, while the other appliances remaining connected

to the common venting system are not in operation.

1.

Seal any unused opening in the common venting

system.

2.

Visually inspect the venting system for proper size and

horizontal pitch and determine there is no blockage or

restriction, leakage, corrosion and other deficiencies

which could cause an unsafe condition.

3.

Insofar as is practical, close all building doors and

windows and all doors between the space in which the

appliances remaining connected to the common venting

system are located and other spaces of the building.

Turn on clothes dryers and any other appliance not

connected to the common venting system. Turn on

any exhaust fans, such as range hoods and bathroom

exhausts, so they operate at maximum speed. Do

not operate a summer exhaust fan. Close fireplace

dampers.

4.

Place in operation the appliance being inspected. Follow

the lighting instructions. Adjust thermostat so appliance

will operate continuously.

5.

Test for spillage at the draft hood relief opening after

5 minutes of main burner operation. Use the flame of

a match or candle, or smoke from a cigarette, cigar or

pipe.

6.

After it has been determined that each appliance

remaining connected to a common venting system

properly vents when tested as outlined above, return

doors, windows, exhaust fans, fireplace dampers and

any other gas burning appliances to their previous

condition of use.

7.

Any improper operation of the common venting system

should be corrected so the installation conforms with

the National Fuel gas Code, ANSI Z223.1/NFPA 54,

and/or the Natural Gas and Propane Installation Code,

CAN/CSA B149.1. When re-sizing any portion of the

common venting system, the common venting system

should be re-sized to approach the minimum size

determined using the appropriate tables in Chapter 13

of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,

and/or the Natural Gas and Propane Installation Code,

CAN/CSA B149.1.

1.

Vent pipe must slope upward from boiler not less then

¼ inch per 1 foot to the vent terminal.

2.

Horizontal portions of venting system shall be

supported rigidly every 5 feet and at elbows. No portion

of vent pipe should have any dips or sags.

3.

Boiler series is classified as a Category I. Vent

installation shall be in accordance with "Venting of

Equipment," of the National Fuel Gas Code, ANSI

Z223.1/NFPA 54, or "Venting Systems and Air Supply

for Appliances," of the Natural Gas and Propane

Installation Code, CAN/CSA B149.1, or applicable

provisions of the local building codes.

4.

Inspect chimney. Verify chimney is constructed

according to NFPA 211. Vent or vent connector shall

be Type B or metal pipe having resistance to heat and

corrosion not less than that of galvanized sheet steel or

aluminum not less than 0.016 inch thick (No. 28 Ga).

5.

Connect flue pipe from draft hood to chimney. Bolt or

screw joints together to avoid sags. Flue pipe should

not extend beyond inside wall of chimney. Do not

install manual damper in flue pipe or reduce size of

flue outlet except as provided by the latest revision of

ANSI Z223.13 or CAN/CSA B149.1. Protect combustible

ceiling and walls near flue pipe with fireproof insulation.

Where two or more appliances vent into a common

flue, the area of the common flue must be at least

equal to the area of the largest flue plus 50 percent of

the area of each additional flue.

6 - VENT INSTALLATION

7 - VENT SYSTEM MODIFICATION

WARNING

Boiler and venting installations shall be performed

by a qualified expert and in accordance with the

appropriate manual. Installing or venting boiler

or other gas appliance with improper methods or

materials may result in serious injury or death due

to fire or to asphyxiation from poisonous gases such

as carbon monoxide with is odorless and invisible.

!

WARNING

Do not connect boiler to any portion of mechanical

draft system operating under positive pressure.

!

This manual is related to the following products: