Systems Design Technical Guide

Interconnected System

7

Personal Computer with Prism II Software

A computer interface can also be used in conjunction with the other
operator interfaces previously described or by itself. The PC used
can be a laptop or desktop computer. Orion Prism II software must be
installed on the PC. Orion Prism Software is available free of charge
at our website, www.orioncontrols.com. In order to use an on site
or remote PC for programming and monitoring of the controller, a
CommLink 5 or USB-Link 2 must also be purchased and installed.
For remote computer connection via an intranet or Internet you would
purchase and install the CommLink with IP Module. Both an on site
and remote PC can be used together if desired.

COMMLINK 5

OR COMMLINK 5 W/ IP MODULE

PERSONAL COMPUTER

WITH PRISM II SOFTWARE

HVAC CONTROLLER - TYP.

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER
SETTINGS

WattMaster Label

#LB102033-01

OE332-23-VCMX-A VCM-X CONTROLLER

WA
RN
IN

G

OBSERVE

POLARITY

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label
#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER
SETTINGS

WattMaster Label

#LB102033-01

OE332-23-VCMX-A VCM-X CONTROLLER

WA
RN
IN

G

OBSERVE

POLARITY

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label
#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER
SETTINGS

WattMaster Label

#LB102033-01

OE332-23-VCMX-A VCM-X CONTROLLER

WA
RN
IN

G

OBSERVE

POLARITY

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label
#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER
SETTINGS

WattMaster Label

#LB102033-01

OE332-23-VCMX-A VCM-X CONTROLLER

WA
RN
IN

G

OBSERVE

POLARITY

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label
#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER
SETTINGS

WattMaster Label

#LB102033-01

OE332-23-VCMX-A VCM-X CONTROLLER

WA
RN
IN

G

OBSERVE

POLARITY

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label
#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

Interconnected with HVAC Unit Controllers with

CommLink 5 or CommLink 5 with IP Module

Using PC and Prism II Software

Prism II Feature Summary

Prism II provides a broad set of features:

On-site, remote modem, or TCP/IP communications

User programmable description for every piece of
equipment and user-defi ned custom screens

Automatic retrieval of trend logs and export capa-
bility to spreadsheet and database programs

Alarm Logs maintained on disk

Alarm E-mail capability

Encrypted History Logs

Computer System Requirements

To use Prism II you must have a computer that meets or exceeds the
following requirements:

Operating System

Microsoft

®

Windows

®

2000/ Windows

®

Vista, or

Windows

®

7

NOTE:

Prism II is not intended for a server/client

environment.

Minimum Hardware

Windows

®

compatible computer

Pentium 2 GHz Processor ( Pentium 4 2 GHz or
greater,

Recommended

)

1 GB RAM or greater)

120 MB hard drive space

XVGA (1024 x 768) adapter and monitor
(1280 x 1024,

Recommended

)

Network card for TCP/IP connection when IP
Module is used.

Communication Device Options

As previously stated, some features require additional devices in
order to operate. These are listed below along with a description of
how they function with the Interconnected system.

MiniLink Polling Device

The MiniLink Polling Device is required when you are using the
Modular System Manager operator interface and require the Modu-
lar System Manager LED lights to indicate alarm and/or override
conditions. This is the only function the MiniLink PD provides for
the Interconnected system.

CommLink 5 or CommLink 5 with IP Module

The CommLink 5 is required if you want to connect an on site and/
or remote PC to the system. If you require a remote PC to be used
to interface to the system, you will also need an IP Module. The
IP Module is used with the CommLink to provide for a remote PC
to interface to the system via a local intranet or the Internet. The
IP Module will allow up to 4 computer TCP/IP connections to be
operating at the same time. The CommLink or CommLink with IP
Module is also required for alarm notifi cation.

USB-Link 2

The USB-Link 2 (OE366) is a portable device that is used as an in-
terface to connect your computer to WattMaster controllers without
the need for a CommLink.

The USB-Link 2 provides a direct link to enable you to view the
status and confi gure and adjust the setpoints of any controller on
the control system communications loop using Prism II software.

The USB-Link 2 is small in size and is powered by the USB port of
the computer it is plugged into, making it completely portable and
allowing connection to the system from any controller.

Add-On Controller Requirements

If you wish to use any of the Add-On Controllers on your system,
you must use a PC with the Prism II software installed for pro-
gramming and monitoring of the controllers. These devices cannot
be programmed or monitored from the Modular System Manager,
System Manager TS II, or Modular Service Tool SD.

The Add-On Controllers that require a PC and Prism II software for
programming and monitoring are:

GPC-X Controller

GPC-XP Controller

Lighting Controller

Prism II Operator Interface & Communication Devices