Networked single loop system, Communication devices & add-on controllers, Systems design technical guide 12 – Orion System Systems Design User Manual
Page 12: Communication device options, Add-on controller requirements
![background image](https://www.manualsdir.com/files/800433/content/doc012.png)
Zone
Zone
Networked Single Loop System
Systems Design Technical Guide
12
Networked Single Loop with HVAC Unit
Controllers and Non-Modular VAV/Zone
Controllers with MiniLink PD and CommLink 5
or CommLink 5 with IP Module
Using PC and Prism II Software
Communication Device Options
As previously stated, some features require additional devices in
order to operate. The Networked Single Loop system requires that
you have either a CommLink 5 or MiniLink PD or both installed
on the system for correct operation. Other features for each device
are listed in the following paragraphs along with a description of
how they function with the Networked Single Loop control system.
MiniLink Polling Device
The MiniLink Polling Device is required when you are using the
Modular System Manager operator interface and require the Modu-
lar System Manager LED lights to indicate alarm and/or override
conditions. It is also required if you are using the System Manager
Touch Screen II and desire the ALARM button to operate on the
SMTS II Main Screen. The MiniLink PD is also required if you
have VAV/Zone controllers and are going to confi gure them into a
zoned (voting) system.
HVAC CONTROLLER, TYP.
NON-MODULAR
VAV/ZONE CONTROLLER, TYP.
EPROM
U3
U5
RAM
C
X
2
1
U2
R
1
C3
U4
CX3
CX4
YS101818P552
PROCESSORPBOARD
CX5
C1
U1
R2
CX1
CX6
WDOG
U6
PHILIPS
D
1
P1
X1
C2
C4
0-10V
4-20mA
THERM
R
27
R
31
D
4
G
N
D
24V
A
C
TB
1
D5
C11
U12
LED 2
POWER
V
1
R
25
R
26
C7
C
X
15
C
X
13
PROC.
DRIVER
LOOP
DRIVER
LOCAL LOOP
G
N
D
A
IN
2
A
IN
1
+5V
T
B2
P4
OFF=0-5V
AIN2
AIN1
0-10V
4-20mA
THERM
TB
3
U
15
LD5
LD6
U
13
C8
LED 1
RV1
R
4
V
R
EF
C
X
2
U11
YS101900PMINILINK
POLLING
DEVICE
REV. 1
OFF
1 2 4 8 16 32
C
X
14
NETWORK
DRIVER
RN3
SH
LD
SH
LD
T
T
TB
4
R
R
U14
NETWORK
LOOP
P
5
AD
D
P
3
R
24
LD4
C9
U10
RN2
SW1
R30
X2
R29
R28
C10
U6
C
X6
C
X1
U7
U1
X1
C3
C1
R
3
CX7
MINILINK PD
COMMLINK 5 OR
COMMLINK 5 WITH
IP MODULE
PERSONAL COMPUTER
WITH PRISM II SOFTWARE
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
S
TAT
GND
24V
AC
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
S
TAT
GND
24V
A
C
R
SHLD
T
TB2
REC
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
CommLink 5 or CommLink 5 with IP Module
The CommLink 5 is required if you want to connect an on site and/
or remote PC to the system. If you require a remote PC to be used
to interface to the system, you will also need an IP Module. The
IP Module is used with the CommLink to provide for a remote PC
to interface to the system via a local intranet or the Internet. The
IP Module will allow up to 4 computer TCP/IP connections to be
operating at the same time. The CommLink or CommLink with IP
Module is also required for alarm notifi cation.
USB-Link 2
The USB-Link 2 (OE366) is a portable device that is used as an
interface to connect your computer to WattMaster controllers.
The USB-Link 2 provides a direct link to enable you to view the
status and confi gure and adjust the setpoints of any controller on
the control system communications loop using Prism II software.
The USB-Link 2 is small in size and is powered by the USB port
of the computer it is plugged into, making it completely portable
and allowing connection to the system from any controller. In order
to view all controllers on a Networked System, a CommLink must
be installed.
Add-On Controller Requirements
If you wish to use any of the Add-On Controllers on your system,
you must use a PC with the Prism II software installed for pro-
gramming and monitoring of the controllers. These devices cannot
be programmed or monitored from the Modular System Manager,
System Manager TS II, or Modular Service Tool SD.
The Add-On Controllers that require a PC and Prism II software for
programming and monitoring are:
•
GPC-X Controller
•
GPC-XP Controller
•
Lighting Controller
Communication Devices & Add-On Controllers