Systems Design Technical Guide

29

USB-Link Connections & Wiring

Figure 11: Computer Connections Using USB-Link 2

Networked Multiple Loop System Using USB-Link 2 & Computer

Adapter

Supplied With USB-Link 2

PL101904

Adapter

Supplied With USB-Link 2

PL101905

Mini-DIN Cable

Mini-DIN Cable

Use The

Adapter To Plug In To A Terminal Socket And Connect

The USB-Link 2 On Boards That Don’t Have A Female Mini-DIN Plug Connection.

This Only Allows Communications With The Board It Is Connected To

PL101904

NOTE:

.

Use The

Adapter And Wire To A Terminal Block

To Connect The USB-Link 2 To The Local Communications Loop

All Controllers

That Are Connected To The System

P 101905

L

On Boards That Don’t Have A Female Mini-DIN Plug Connection.

This Allows Communications With

. See Note 1.

NOTE:

USB-Link 2

Controller With

Mini-DIN Plug

USB Cable

Supplied With

USB-Link 2

Connect Type A Cable End To

USB Port On Desktop Or Laptop

Personal Computer.

USB Drivers Supplied With The USB-

Link 2 Must Be Installed On Your Computer

Before USB-Link 2 Can Be Used.

NOTE:

Connect Type B Cable End

To USB Port On USB-Link 2.

Connect Mini-DIN Cable End

To Mini-DIN Port On USB-Link.

Configuration Switch

Must Be Set To Stand Alone Or Network

Depending On Your Installation

Mini-DIN Cable

Supplied With

USB-Link

Connect The USB-Link 2

Mini D

Cable To The

- IN

Connector On

Controllers That Are Supplied

With Them.

All

Controllers That Are

Connected To The System

- IN

Female

Mini D

Plug

This Allows

Communications With

.

NOTE:

STAND ALONE

NETWORK

SHLD

SHLD

T

T

R

R

Communication Speed Switch

Must Be Set To Low or High Speed

Depending on Your Controller’s

Baud Rate.

WARNING! Make Sure To Install
The USB Drivers Before Connecting
The USB-Link 2 To Your Computer.

To Next HVAC Unit

Controller On Loop

Up To 60 Controllers

Can Be Interconnected.

Line Voltage

HVAC Unit Controller

24 VAC
(8 VA)

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label

#LB102033-01

OE332-23-VCMX-A VCM-X CONTROLLER

WA
RN
IN

G

OBSERVE

POLARITY

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label
#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

Computer

(By Others)

With Prism
II Software

Installed