Setra, 2( ² %xloglqj 3uhvvxuh 6hqvru, Description – Orion System OE217-00 User Manual
Page 32
Form: ORION-OE258-6-BuildingPressureSensor-1B.doc
Page
1 of 1
Description
The OE258 Building Static Pressure Sen-
sor is used to sense building pressure in
applications where monitoring of the
building static pressure is required to in-
sure the building maintains the proper air
pressurization.
The OE258 Building Pressure Sensor
case is molded from fire retardant glass
filled polyester. The sensor utilizes a ten-
sioned stainless steel diaphragm and in-
sulated stainless steel electrode. This
arrangement allows up to 10 PSI over-
pressure without damage to the unit. The
sensor provides a 0.0 to 5.0 VDC output
in response to a –0.25 to +0.25 inch WC
pressure differential. Accuracy is
±
1% of
full scale of the sensor.
For easy wiring the OE258 Building Static
Pressure Sensor has (3) 6-32 screw ter-
minal wiring connectors. The sensor has
(2) ¼” barbed fittings provided for the
connection of tubing to the high and low
pressure ports.
The OE258 Static Pressure Sensor is
designed to be mounted to a flat surface
by means of the (2) 0.156 diameter holes
provided in the sensor casing. For accu-
rate readings the sensor must be
mounted in a vertical position.
Technical Data
OE258 - Building Static
Pressure Sensor
Operating Pressure
Range
-0.25” WC to +0.25” WC
Pressure Differential
Power Input
Signal Output
9-30 VDC
0 to 5 VDC
Operating Temp
0
°
F to 150
°
F
Hysteresis
±
0.1% of full scale
Circuit
3 Wire
Non-repeatability
±
0.05% of full scale
Accuracy
±
1% of full scale
Weight
3 ounces
Three Year Warranty
WattMaster reserves the right to change specifications without notice
HIGH
MODEL 265
LOW
-
+
+
+
1.89
0.95
3.16
2.74
setra
0.95
1.64
0.156 DIA. HOLE
TYP. 2 PL.
2( ² %XLOGLQJ 3UHVVXUH 6HQVRU