beautypg.com

Description, Mounting, Page – Orion System OE217-00 User Manual

Page 12: 1 of 1

background image

Form: ORION-StandardRoomSensor-1D.doc

Page

1 of 1

Description

The patented design, OE21x series Standard Room Sen-
sor provides accurate sensing of the room temperature.
Its design allows for flush wall mounting yet rejects the
influence of surface and internal wall temperatures. The
Standard Room Sensor is used in conjunction with the
Orion controllers. Wire terminals are provided on the sen-
sor for connection to the controllers. The Standard Room
Sensor cannot be used for connection to the VAV/Zone
controller. For this application the Modular Room Sensor
must be used. Please see the Orion Modular Room Sen-
sor submittal sheet for information.

Sensors provided with the setpoint adjustment option can
be programmed to allow a temperature range adjustment
of ± 6°F from their standard setpoint. Sensors provided
with the pushbutton override option can be programmed
to provide a timed override duration of up to 8.0 hours.


The Room Sensor’s attractive styling and off white casing
color make it suitable for most building decors. If interior
decoration requires, the Room Sensor casing can also be
painted or wall papered without affecting the sensor's per-
formance. Room Sensors are available in 4 different con-
figurations:

 OE210 Sensor Plain
 OE211 Sensor with Override
 OE212 Sensor with Setpoint Adjustment
 OE213 Sensor with Setpoint Adjustment and

Override

Mounting

The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the
wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold

, may be used to

mount the sensor to the wall surface.

OE210, 211, 212 & 213

Standard Room Sensors




Technical Data

OE210, OE211, OE212, OE213 Standard Room Sensor

Sensor Element

Type III Thermistor
10k ohm @ 77º F

Mounting

Designed to be Flush Mounted to Wall
using Vertical 2” x 4” Handy Box (by others)

Accuracy

0.4º F between 40º F to 95º F

Line Loss

0.25º F max. error, using 22 AWG wire at 1000 ft

Range

-30º F to 150º F

Weight

4 oz.

3 Year Warranty

WattMaster reserves the right to change specifications without notice

OE210

OE211

OE212

OE213

Room Sensor - Plain

Room Sensor

With Override

Room Sensor

With Setpoint Adjust

Room Sensor

With Setpoint Adjust

& Overide

O

O

A

A

O

O

R

R

L

L

M

M

E

E

E

E

C

C

W

W

R

R

R

R

OVR

OVR

0.25“

TMP

GND

AUX

OUT

2.75“

2.00“

Wall Cut-Out Dimensions

When Sensor Is To Be

Mounted Without

Handy Box (By Others)

2.75“

3.25“

4.50“

2.50"

0.88“

O

A

O

R

L

M

E

E

C

W

R

R

This manual is related to the following products: