beautypg.com

Sensor mounting position, Right side lef, Side – Orion System OE217-00 User Manual

Page 18: Iew front

background image

JOB NAME

FILE NAME

G-OE265-13B-OAHUMID-1F.PDF

DATE: 08/25/11

PAGE

DESCRIPTION

Outside Air Humidity Sensor – 0-5 VDC

DRAWN BY: B. CREWS

Notes:

1.) The Outside Air Humidity Sensor Must

Be Mounted In A Vertical Position As Shown

(Sensor Tube Pointing Down).

Water Must

Not Be Allowed To Stand In Sensor Tube,

it Will Cause Erroneous Sensor

Readings. The Sensor will recover when

it dries out. Sensor Must Be Located

Where It Will Not Be Affected By Direct

Sunlight Or Heat Producing Equipment. If

Possible Mount Under Roof Eave Or Similar

Protected Location. If Sensor Is Not

Located As Specified, Erroneous Outside Air

Humidity Readings Will Result.

2.) Unused Conduit Opening(s) Must

Not be Knocked Out to Prevent Dust

or Insects From Infiltrating the Sensor

Electrical Box.

3.) All Wiring To Be In Accordance

With Local And National Electrical

Codes And Specifications.

1 of 2

Installation Instructions:

1.) Place The Outside Air Humidity Sensor Where It Is To Be Mounted. See Note 1 Below For

Important Mounting Information And Considerations. Mark The (4) Mounting Holes. Secure The

Humidity Sensor By Using The Four #10 X 1.5" Self Tapping Screws Included With The Humidity

Sensor.

2.) Open The Cover by Moving the Latch to the Side And Install Your Conduit Connectors. The

Cover Must Always Be Opened Before Attempting To Punch Out The Knockouts.

3.) Connect The Wires To The Corresponding Sensor Wire Leads Per The Wiring Diagram On

Page 2 Of This Drawing. Insert the Wires Into the Sealant Filled Connectors Provided and Crimp.

Lightly Tug on the Wire to Assure a Good Mechanical Connection

4.) Close The Cover by Pushing Down Until the Latch Snaps Into Place. Be Careful Not To Pinch

The Sensor Wires When Closing The Housing Cover.

5.) Verify That You Are Getting A Humidity Reading On Your Control System. Please Note That It

May Take Ten To Twenty Minutes For The Sensor Reading To Stabilize Upon Initial Power Up.

Sensor Mounting Position

OE265-13 BAPI

INCORRECT

CORRECT

INCORRECT

Right

Side

Lef

t

Side

T

op

V

iew

Front

V

iew

V

iew

V

iew

6.70