Description, Mounting, Page – Orion System OE217-00 User Manual
Page 10
Form: ORION-ModularRoomSensor-1F.doc
Page
1 of 1
Description
The patented design, OE21x-02 series Modular Room
Sensor provides accurate sensing of the room tempera-
ture. Its design allows for flush wall mounting yet rejects
the influence of surface and internal wall temperatures.
The Modular Room Sensor is used in conjunction with the
Orion VAV/Zone Controller. Connection between the
VAV/Zone Controller board and the Modular Room Sen-
sor is by means of an RJ-45 Modular Cable. The Modular
Room Sensor cannot be used for connection to the VCM-
X controller. For these applications the Standard Room
Sensor must be used. Please see the Orion Standard
Room Sensor submittal sheet for information.
Sensors provided with the setpoint adjustment option can
be programmed to allow a temperature range adjustment
of ± 6°
F from their standard setpoint. Sensors provided
with the pushbutton override option can be programmed
to provide a timed override duration of up to 8.0 hours.
The Room Sensor’s attractive styling and off white casing
color make it suitable for most building decors. If interior
decoration requires, the Modular Room Sensor casing
can also be painted or wall papered without affecting the
sensor's performance. Modular Room Sensors are avail-
able in 4 different configurations:
OE210-02 - Sensor Plain
OE211-02 - Sensor with Override
OE212-02 - Sensor with Setpoint Adjustment
OE213-02 - Sensor with Setpoint Adjustment and Override
Modular cable from the VAV/Zone Controller to the Modular Room Sensor should not be run in conduit with other
AC line voltage wiring, or with any conductors carrying highly inductive loads.
Mounting
The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the
wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold
, may be used to
mount the sensor to the wall surface.
Technical Data
OE210-02, OE211-02, OE212-02, OE213-02
Modular Room Sensor
Sensor Element
Type III Thermistor
10k ohm @ 77º F
Mounting
Designed to be Flush Mounted to Wall
using Vertical 2” x 4” Handy Box (by others)
Accuracy
0.4º F between 40º F to 95º F
Connection
RJ-45 Modular Female Jack
Range
-30º F to 150º F
Weight
4 oz.
3 Year Warranty
WattMaster reserves the right to change specifications without notice
0.25“
2.75“
2.00“
Wall Cut-Out Dimensions
When Sensor Is To Be
Mounted Without
Handy Box (By Others)
2.75“
3.25“
4.50“
2.50"
0.88“
O
A
O
R
L
M
E
E
C
W
R
R
R2
PJ1
R1
THERM1
REV 0
YS101858
MODULAR
SENSOR
OE210-02, 211-02, 212-02, 213-02
Modular Room Sensors