beautypg.com

Main screen functions, System manager settings, Smts ii for gpc-xp technical guide 12 – Orion System System Manager TS II For GPC-XP User Manual

Page 12: Zone

background image

Zone

Zone

MAIN SCREEN FUNCTIONS

SMTS II for GPC-XP Technical Guide

12

System Manager Settings

Figure 12: System Manager Settings Screen

30

System Manager Settings

Backlight Timeout

Backlight Intensity

System Manager Address

Back

30

Minutes

30

50

%

30

63

One to One Unit Connection

System Manager Version: 1.02

System Manager Settings

Additional system settings are available under the

icon. These include setting the Backlight Timeout, the Backlight
Intensity Percentage, the System Manager Address, and One to One
Unit Connection.

From the Main Screen, touch the

< Settings>

icon.

The System Manager Settings Screen will appear. See
Figure 12.

Backlight Timeout:

This setting is actually a setting for three

separate functions—Backlight Timeout, Main Screen Timeout, and
Passcode Timeout. To set the Backlight Timeout, enter the amount
of time you wish the screen to maintain the active intensity level
after the last touch pad activity occurs. The High limit is 30 and the
Low limit is 0. 0 = No Timeout. The System Manager TS II will
return to the Main Screen display at the same rate as the Backlight
Timeout, except that if set to 0, the Main Screen will display after 2
minutes. The Passcode will timeout at the same rate as the Backlight
Timeout, except that if set to 0, the Passcode will timeout after 2
minutes and will return to System Secured Setting.

Backlight Intensity Percentage:

Enter the percentage of light

level you wish to maintain whenever touch pad activity occurs. The
High limit is 100 and the Low limit is 0.

System Manager Address:

Enter the address of the System

Manager TS II. 0 = Stand Alone Mode. 63 = Network System. 1-60
= Multiple Managers based on the following defi nitions:

Stand Alone

If your System Manager TS II is connected to

one controller and you are not using a CommLink or MiniLink
anywhere on the loop, your system is Stand Alone. If your
System Manager TS II is connected to more than one controller
daisy-chained together and you are not using a CommLink or
MiniLink anywhere on the loop, your system is Interconnected.
If you have either a Stand Alone or Interconnected system,
you must enter

<0>

for Stand Alone Mode. In order to view

all controllers on an Interconnected System, make sure that
One to One Unit Connection, described below, is not selected.

Network—

If you are using this System Manager TS II on a com-

munications loop that has a MiniLink or CommLink installed
and you have a single System Manager TS II for your entire
system, you must enter

<63>

for Network System.

Multiple Managers—

If you are using this System Manager TS

II on a communications loop, have a MiniLink or CommLink
installed, and have more than one System Manager TS II, then
you need to operate in Multiple Managers Mode. Enter the ad-
dress

<1-60>

at which you want this particular System Manager

TS II to be set. When more than one System Manager TS II
is used on a local loop, each must be set with a unique address
different from any other device on that loop. If you want one
of the System Manager TS II’s to be able to indicate alarms for
the entire system, you must enter

<63>

for Network System

for that particular System Manager TS II.

One to One Unit Connection: If your System Manager TS II
is directly connected to the GPC-XP Controller, you may wish to
select this option to bypass the Unit Selection Screen and go directly
to the unit’s Status Screen. The controller must be set to address #1
for this to work. Touch the black box to the left of this item on the
screen to select it. The box will turn white. If you wish to deselect
this option, simply touch the box again.

System Manager Version: The version number of the System
Manager software appears on the bottom menu bar. This version
number is important to know for troubleshooting purposes.