Appendix, Sa controller technical guide, Oe265 series rh sensor testing – Orion System SA Controller User Manual
Page 59

SA Controller Technical Guide
Appendix
59
OE265-11 and -14 RH Sensors
OE265-11 & OE265-14 Relative Humidity Sensor Test-
ing Instructions
Use the voltage column to check the Humidity Sensor while connected
to a powered expansion module. Read voltage with meter set on DC
volts.
Place the “-” (minus) lead on the terminal labeled GND and the “+”
lead on the AIN terminal that the Humidity sensor is connected to on
the Analog Input/Output Expansion Module.
OE265 Series RH Sensor Testing
The chart below is used to troubleshoot the OE265-11 and OE265-14
Relative Humidity Sensors.
OE265-11 & OE265-14 Relative Humidity Transmitters –
Humidity vs. Voltage for 0-5 VDC Sensors
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
0%
0.00
52%
2.60
2%
0.10
54%
2.70
4%
0.20
56% 2.80
6%
0.30
58%
2.90
8%
0.40
60% 3.00
10%
0.50
62%
3.10
12%
0.60
64%
3.20
14%
0.70
66%
3.30
16%
0.80
68%
3.40
18%
0.90
70%
3.50
20%
1.00
72%
3.60
22%
1.10
74%
3.70
24%
1.20
76%
3.80
26%
1.30
78%
3.90
28%
1.40
80%
4.00
30%
1.50
82%
4.10
32%
1.60
84%
4.20
34%
1.70
86%
4.30
36%
1.80
88%
4.40
38%
1.90
90%
4.50
40%
2.00
92%
4.60
42%
2.10
94%
4.70
44%
2.20
96%
4.80
46%
2.30
98%
4.90
48%
2.40
100%
5.00
50%
2.50
Table 5: Humidity/Voltage for OE265-11 & -14
Humidity Sensors