SA Expansion Module Input Wiring
Figure 16: OE333-23-SA – SA Expansion Module Input Wiring
SA Expansion Module
Two different Expansion Modules are available for use with the SA
Controller to provide additional inputs and outputs beyond those found
on the SA Controller.
The SA Expansion Module ( OE333-23-SA Controller) provides 8 Binary
Inputs, 4 Analog Inputs, 5 Analog Outputs, and 4 Confi gurable Relay
Outputs. See Figures 16 and 17 for complete wiring details.
Emergency Shutdown - N.C. Input
Drain Pan Overflow A - N.O. Input
Drain Pan Overflow B - N.O. Input
Water Proof of Flow B - N.O. Input
Air Proof Of Flow - N.O. Input
Remote Forced Occupied - N.O. Input
VOUT (0-5V)
0-5V
GND
GND
VIN
VAC OR DC
Water Proof of Flow A - N.O. Input
Dirty Filter - N.O. Input
AI2
AI3
AI4
B 7
I
B 6
I
B 5
I
B 3
I
B 4
I
B 1
I
B 2
I
Modular Cable
Connect To SA Controller
Modular Cable
Connect To E-BUS Distribution
Module (When Used)
24 VAC
GND
Entering Air
Humidity Sensor
Indoor Air
Humidity Sensor
10 VA Minimum Power Required
For SA Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity
will result in damage to one or more of the boards. Expansion Module must be wired in such a way that the
expansion module and the controller are always powered together. Loss of power to the expansion module will
cause the controller to become inoperative until power is restored to the expansion module.
SA Expansion Module
AI1
GND
GND
BI8
SA
See Humidity Sensor Wiring
Details For Complete Wiring
Information.
See Suction Pressure
Transducer Wiring Details For
Complete Wiring Information.
Additional Suction
Pressure Sensor Required
On Dual Units Only.
RD
RD
WH
WH
BK
BK
Suction Pressure
Transducer #1
Suction Pressure
Transducer #2
Splice Wire As Required To Reach
From Transducer Location To
Expansion Module Location
The 12-Relay Expansion Module ( OE358-23-12R) provides for 12
Dry Contact Confi gurable Relay Outputs. See Figure 25 for complete
wiring details.
The expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.
Revised 6/21/11