beautypg.com

Three phase ups systems 6.0 interface – OnLine Power Battery Backup System User Manual

Page 60

background image

OLP

Three Phase UPS Systems

6.0 INTERFACE

6-2

FAULT – Closed when the UPS encounters a fault condition, such as high DC

shutdown, short circuit, fuse/over-heat, overload shutdown, emergency
stop, inverter abnormal, bypass on shutdown. The contact is latched until
manual reset (off switch) or 30 seconds after the fault condition is
removed.

SS – Closed when the inverter static switch is conducting, open when the

reserve static switch is conducting (The two static switches will never
conduct simultaneously).

BYPASS – Closed when the maintenance bypass breaker is closed, open when

the breaker is opened.

BACK-UP – Closed when the inverter (running) is being backed up by the

battery.

BATL – Closed when the inverter is using battery power and the batteries are

about to be exhausted.

COM –This contact can be configured as the OR result of the signals

described above. SWR2-1 (dip-switch pin 1) ~ SWR2-7 (dip-switch pin 7)
can select one of the seven signals described above and SWR2-8 is the
COM enable switch. Please refer to the dip-switch of SWR2 on the 3R
PCB and the following examples and diagram.