Three phase ups systems 2. technical – OnLine Power Battery Backup System User Manual
Page 31
OLP
Three Phase UPS Systems
2. TECHNICAL
3
KVA 80
100
120
160
OVERALL CHARACTERISTICS
OVERALL EFFICIENCY
92.5%
92.5%
93%
93%
OPERATING ENVIRONMENT:
- TEMPERATURE
0 -40℃ ( 32 - 104℉ )
- HUMIDITY
0% - 90% ( NON–CONDENSING )
- ALTITUDE
<1500 M ABOVE SEA LEVEL
TYPICAL HEAT
DISSIPATION (BTU)
5280 6600 7900 10,533
WEIGHT(lbs) (No Battery) 1760
2420
2860
3300
DIMENSION:
- HEIGHT
62”
- WIDTH
43”
- DEPTH
22”
- AUDIBLE NOISE
< 65 dBA (@ 1 m)
STANDARDS:
- EN50091-1,-2
YES
- FCC CLASS A
YES
PROTECTIONS:
- SHORT CIRCUIT
RECTIFIER, RESERVE, BYPASS NFB
- LIGHTNING
MOV
- EMC FILTER
INPUT & OUTPUT
- GALVANIC ISOLATION
BETWEEN INPUT & OUTPUT
DATA DISPLAY BY LCD
YES
INDICATIONS & ALARMS:
- LED,LCD,BUZZER
YES
DRY CONTACT
YES
BATTERY START
YES
☆ All specifications are subject to change without prior notice.