Online power – OnLine Power Protector 3 User Manual
Page 79
OnLine Power
6-40
6.19 OPTIONAL ECC - EMERGENCY CIRCUIT CONVERTER – P/N 9100-1501
6.19.1 Installation
Indoor use only. Simple and fast installation in ceiling or wall mounted standard single gang E-box . Installation
must be performed by a qualified electrician per Installation, Operation and Maintenance Instructions, provided
with the ECC.
6.19.2 Operation
When used with an inverter system, the ECC is designed to allow you the ability to turn off ALL of the lighting in a
given area via the local switch, and still provide emergency lighting during a power failure. The device will provide
single phase power from the emergency source to the designated emergency fixtures regardless of their current
status (on or off), thereby insuring safe egress from the facility at all times. The automatic Diagnostic feature will
confirm the emergency system is ready to provide back up power.
6.19.3 Specification
Description:
ECC - EMERGENCY CIRCUIT CONVERTER OPTION
Part Number: 9100-1501-01 - 120 VAC
9100-1501-01- 277 VAC
Rating:
120 VAC - 20 A Ballast load, 1000 W Tungsten Lamp load, 20 A, 1 HP
277 VAC – 20 A Ballast load, 1800 W Tungsten Lamp load, 20 A, 1.5 HP
Operating Temperature: 20 to 150 F
Flame rating:
UL 94V-O
Size:
2.75”W x 4.75”H x 1.75”D (overall)
Low profile – recessed portion is only 1.5” deep
Color:
White
Weight:
8 oz.
EMERGENCY
POWER
UTILITY
POWER
TEST SWITCH
ILLUSTRATION 6-12: ECC EMERGENCY CIRCUIT CONVERTER