beautypg.com

Description of components – Nortec NH Series User Manual

Page 7

background image

Introduction | 4

Description of Components

Table 1: Humidifier Components

Component

Function of Component

Auxiliary Drain
Switch

Drains water from boiling tank by activating drain pump. Note that initiating a
drain in this manner will not induct Drain Water Cooling.

Boiling Tank

Holds resistive elements submerged in water. Current traveling along the
internal element wire generates heat which is used to generate steam.

Condensate
Return

Provides a connection to return condensate to humidifier.

Contactor

Turns On/Off power to boiling tank elements.

Drain Pump

Drains water from boiling tank.

Drain Water
Cooling Valve

Adds cold supply water to water draining from boiling tank to temper drain
water to a maximum of 140ºF (60ºC).

Driver Board

Provides input and output connections to humidifier components.

Fill Cup

Provides an air gap for backflow prevention.

Fill Valve

Controls flow of water into humidifier.

High Voltage
Terminal Block

Primary power connection from remote disconnect to humidifier.

High Voltage
Transformer

Steps primary voltage down to 24 VAC for the controller and internal
components such as the fill valve and drain pump.

On/Off Switch

Turns power On/Off to humidifier controller. Note: Turn off humidifier
disconnect to shut off primary power to the humidifier.

Remote Relay
Board (option)

Provides a terminal strip to dry contacts which open/close to indicate the
humidifier is on, humidifying, needs service, or is in a fault condition.

Scale Tank

Scale created inside the boiling tank (on the elements and the side walls)
breaks off and gravitates to the scale tank for easy disposal.

Scale Tank
Drain Spigot

Manually activated drain spigot used to empty the scale tank of water before
removing and emptying tank of collected scale.

Solid State
Relay (optional)

Solid State Relays offer shorter cycles when turning the resistive elements On
and Off. Recommended for humidification applications requiring high
accuracy.

Steam Outlet

Connect to steam line with steam hose.

User Interface

Controls all functions of the humidifier operation and provides user ability to
modify configuration of the humidifier.