13 | Installation

Note:

• Drain water is very hot, do not drain to public sink.

• Use material suitable for 212ºF (100ºC) for drain and condensate lines.

Plumbing






All water supply and drain line connections should be installed in accordance with local

plumbing codes.

Supply water should have pressure between 30 and 80 psi

g

and have a hardness

between 0 and 12 gr/gal. Various types of supply water may be used: soft water, de-
ionized, reverse osmosis, or potable.

Install water shut-off valve and union before humidifier to facilitate servicing.

The drain line should not end in a sink used frequently by personnel, or where plumbing

codes prohibit. Route to a floor drain or equivalent for safety reasons.

Ensure drain line is adequately sized to provide free and easy draining. Ensure air gap is

installed as shown. A restricted drain can cause the boiling tank to become heavily
concentrated with minerals and may result in poor operation or water backing up at the
air gap.

Figure 7: Water Supply and Drain Connection