beautypg.com

Nortec NH Series User Manual

Page 42

background image

39 | Start Up

d. Working Hours

1. Total of working hours elapsed since initial commissioning of the humidifier.

e. Time Remaining to minor/major service

1. Time remaining (in hours) before the next minor/major service.

Time to maintenance can be adjusted to suit water conditions.

The stated times are based on 100% steam capacity. If the operation is at a lower

capacity, the time should be extended accordingly. For example, average capacity of
50% would double the time to maintenance. Average capacity of 33% would triple the
time to maintenance. The servicing intervals are set up using the rotary switch “S2” on
the control board.

Table 10: Maintenance intervals with rotary switch S2

S2 Position

Interval Minor

Maintenance

Interval Major

Maintenance

0

200 hours

600 hours

1

300

600

2

300

900

3

450

900

4

400

1200

5

600

1200

6

500

1500

7

750

1500

8

3000

3000

9

6000

6000

NOTE: S2 rotary switch is set at factory to “0”.

0

200 hours

600 hours

1

300 hours

600 hours

2

300 hours

900 hours

3

450 hours

900 hours

4

400 hours

1200 hours

5

600 hours

1200 hours

6

500 hours

1500 hours

7

750 hours

1500 hours

8

3000 hours

3000 hours

9

6000 hours

6000 hours

Position

S2

Interval Minor

Maintenance

Interval Major

Maintenance

10

0

15

0

20

0

30

0

45

0

6

0

90

0

135

0

180

0

S2 Setting

NHRS

Model

Value Setting

Factory Setting

NHRS Main PCB

Maintenance Interval
Adjustment [S2]

Figure 30: Maintenance interval adjustment S2