39 | Start Up
d. Working Hours
1. Total of working hours elapsed since initial commissioning of the humidifier.
e. Time Remaining to minor/major service
1. Time remaining (in hours) before the next minor/major service.
Time to maintenance can be adjusted to suit water conditions.
The stated times are based on 100% steam capacity. If the operation is at a lower
capacity, the time should be extended accordingly. For example, average capacity of
50% would double the time to maintenance. Average capacity of 33% would triple the
time to maintenance. The servicing intervals are set up using the rotary switch “S2” on
the control board.
Table 10: Maintenance intervals with rotary switch S2
S2 Position
Interval Minor
Maintenance
Interval Major
Maintenance
0
200 hours
600 hours
1
300
600
2
300
900
3
450
900
4
400
1200
5
600
1200
6
500
1500
7
750
1500
8
3000
3000
9
6000
6000
NOTE: S2 rotary switch is set at factory to “0”.
0
200 hours
600 hours
1
300 hours
600 hours
2
300 hours
900 hours
3
450 hours
900 hours
4
400 hours
1200 hours
5
600 hours
1200 hours
6
500 hours
1500 hours
7
750 hours
1500 hours
8
3000 hours
3000 hours
9
6000 hours
6000 hours
Position
S2
Interval Minor
Maintenance
Interval Major
Maintenance
10
0
15
0
20
0
30
0
45
0
6
0
90
0
135
0
180
0
S2 Setting
NHRS
Model
Value Setting
Factory Setting
NHRS Main PCB
Maintenance Interval
Adjustment [S2]
Figure 30: Maintenance interval adjustment S2