43 | Start Up
o. Control Signal
1. Range of the active analog signal in Volts or milliamps.
NOTE: The range of the analog signal may be adjusted using the rotary switch
“S3” on the control board.
Table 13: Control signal settings with rotary switch "S3"
S3 Position
Signal
0
No signal selected
1
Spare
2
0-5 VDC
3
0-10 VDC
4
Other
5
1-5 VDC
6
2-10 VDC
7
Other
8
4-20 mA
9
0-20 A
Figure 32: Control signal setting S3