15 | Installation
Steam Lines and Condensate Return
The following instructions must be followed for installation of steam lines for ASD, BSD, CSD,
SAM-e, and Remote Blower Packs. Failure to used material in Table 6 and Table 7 on page 16,
or failure to follow any other steam line installation instructions, will result in improper operation
and could void warranty.
Table 6: Recommended Maximum Length of Steam Line
NHRS
Unit
Size
Steam
Output
(lbs/hr)
Distance
ft (m)
Possible
Loss
ft (m)
Steam
Line
Size
010
10
15 (4.5)
2 (0.6)
1.5”
015
15
17.5 (5)
2.25 (0.7)
020
20
20 (6)
2.5 (0.8)
030
30
25 (7.5)
3 (0.9)
045
45
35 (10.5)
4 to 5 (1.2 to 1.5)
065
65
45 (13.5)
5 to 10
(1.5 to 3.0)
090
90
50 (15)
135
135
50/tank (15)
2 x 1.5”
180
180
50/tank (15)
NOTES:
1) This chart gives the maximum length of recommended steam line by unit size.
2) The use of steam line other than copper, stainless steel, or Nortec steam hose will void the
warranty and may cause adverse effects regarding the operation of the humidifier.
3) Nortec steam line shall only be used for steam line runs of 10 ft (3m) or less.
4) Long steam runs affect accuracy of humidifier and its ability to quickly respond to changes in
demand. When tight control is required, ensure steam line run is as short as possible.
5) NHRS 135 and 180 have two tanks.
Danger:
The NHRS is an atmospheric humidifier that will only operate properly when its steam
distribution system is installed so that it provides no significant backpressure.
Installing the NHRS in such a way that backpressure can develop during operation
could result in serious injury or damage to property.