15 | Installation

Steam Lines and Condensate Return

The following instructions must be followed for installation of steam lines for ASD, BSD, CSD,
SAM-e, and Remote Blower Packs. Failure to used material in Table 6 and Table 7 on page 16,
or failure to follow any other steam line installation instructions, will result in improper operation
and could void warranty.








Table 6: Recommended Maximum Length of Steam Line

NHRS

Unit

Size

Steam

Output

(lbs/hr)

Distance

ft (m)

Possible

Loss

ft (m)

Steam

Line

Size

010

10

15 (4.5)

2 (0.6)

1.5”

015

15

17.5 (5)

2.25 (0.7)

020

20

20 (6)

2.5 (0.8)

030

30

25 (7.5)

3 (0.9)

045

45

35 (10.5)

4 to 5 (1.2 to 1.5)

065

65

45 (13.5)

5 to 10

(1.5 to 3.0)

090

90

50 (15)

135

135

50/tank (15)

2 x 1.5”

180

180

50/tank (15)

NOTES:

1) This chart gives the maximum length of recommended steam line by unit size.
2) The use of steam line other than copper, stainless steel, or Nortec steam hose will void the

warranty and may cause adverse effects regarding the operation of the humidifier.

3) Nortec steam line shall only be used for steam line runs of 10 ft (3m) or less.
4) Long steam runs affect accuracy of humidifier and its ability to quickly respond to changes in

demand. When tight control is required, ensure steam line run is as short as possible.

5) NHRS 135 and 180 have two tanks.


Danger:
The NHRS is an atmospheric humidifier that will only operate properly when its steam
distribution system is installed so that it provides no significant backpressure.
Installing the NHRS in such a way that backpressure can develop during operation
could result in serious injury or damage to property.