41 | Start Up

Table 12: Water quality

Water

Parameters

Potable Water

Treated Water

Conductivity

0-1500

Siemens

0-50

Siemens

Hardness

12 grains per gallon

0 grains per gallon

Silica

12 ppm

0 ppm

pH

6.5-7.5

7

Chlorides

> 50 ppm

> 25 ppm


Nortec recommend performing a semi-annual water analysis to ensure optimal
performance.

g. Stand-by Heating (also known as “Keep Warm”)

1. Stand-by Heating activated (“on”) or deactivated (“off”).

NOTE: If stand-by heating is active, the water temperature in the steam tank is
constantly kept at approximately 158ºF (70ºC) by the control board.

h. Capacity Limitation

1. To change the Power Limit (Maximum Capacity), complete the following:

• Press both arrow keys simultaneously,

• Enter code “8808”,

• Change to desired value, and

• Press both arrow keys simultaneously.

i. Inlet Valve Correction

1. Set inlet valve correction (cycle ratio) in % of standard setting value to balance
out water pressure variations. Contact factory for more details.

j. Soft Start

1. Soft Start activated (“on”), consult factory. Deactivated (“off”), factory default.