Timer mode
POUT x MODE: POUT TIMER
AKT.: High TIME 1(-3)
Time 1 ON : 10:50:00
OFF: 11:00:00
Time 2 ON : 13:00:00
OFF: 14:00:00
Time 3 ON : 23:45:00
OFF: 09:30:00
If Timer mode is selected, a window as shown above is displayed. The switching plan
is assigned per day. Three turn-on and turn-off times are programmable for each
output. If a switching time has to be configured, only the turn-on and turn-off time
must be programmed. Thus the example shows switching times from 10:50 to 11:00,
13:00 to 14:00 and 23:45 to 09:30. A turn-off time earlier than the turn-off time would
cause the output to be enabled over midnight. For example a program 'On Time'
10:45:00, 'Off Time' 9:30:00 would cause an active ouput from 10:45 to 9:30 (the
next day!). If one or more of the three switching times are unused just enter the same
time into the fields 'On Time' and 'Off Time'. In this case the switch time does not
affect the output.
Single Pulse
Selecting Single Pulse generates a single pulse of defined length once per day.
POUT x MODE: SING. PULS
AKT.: High LNG.: 00.10 sec
SINGLE SHOT
TIME: 12:00:00
You can enter the time when the pulse is generated in the field 'Single Shot Time'.
The value in field 'Length' determines the pulse duration. A pulse duration from 10
msec to 10 sec in steps of 10 msec can be selected.
The example shows a single pulse at 12:00 every day with a duration of 100 ms.