LonWorks Communication Module (CME-LW01) Instruction Sheet

Lonworks is a registered trademark of Echelon Corporation.
Please thoroughly read and understand the following contents to ensure correct use before operation.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or

download the most updated version at http://www.delta.com.tw/industrialautomation

A. Introduction

Device CME-LW01 is used for communication interface between
Modbus and LonTalk. CME-LW01 needs be configured via
LonWorks network tool first, so that it can perform the function on
LonWorks network. No need to set CME-LW01 address.
This manual provides instructions for the installation and setup for
CME-LW01 that is used to communicate with Delta VFD-E
(firmware version of VFD-E should conform with CME-LW01
according to the table below) via LonWorks Network. The content
of this instruction sheet may be revised without prior notice.
Please consult our distributors or download the most updated
version at http://www.delta.com.tw/industrialautomation.

Delta AC Drive

Series

Firmware Version

VFD-E

Version 2.02 or higher

B. Dimensions

5

7.

3

[2

.2

6]

72.2 [2.84]

59

.7

[2

.3

5]

9.

5

[0

.3

7]

3.5 [0.14]

34.8 [1.37]

SP

CME-LW 01

C. Specification

Power supply

16-30VDC, 750mW

Communication

Modbus in ASCII format, protocol: 9600, 7, N, 2

LonTalk

free topology with FTT-10A 78 Kbps

LonTalk terminal

4-pin terminal, wire gauge: 28-12 AWG, wire strip
length: 7-8mm

RS-485 port

8 pins with RJ-45

D. Wiring

SP

CME-LW01

Power LED SP LED

Service LED

Service Pin

1: Reserved

2: EV

3: GND

4: SG-

5: SG+

6: Reserved

7: Reserved

8: Reserved

LonTalk

1 2 3 4

LonTalk

Terminal definition for LonTalk system

Terminal

Symbol

Function

1

2

3

4

These are twisted pair cables
to connect to LonTalk system.
Terminals 1 and 2 should be
used as one group, and the
same for terminals 3 and 4.

E. LEDs

Indications

There are three LEDs in front panel of CME-LW01. If the
communication is normal, power LED, SP LED should be green
(red LED means abnormal communication) and service LED
should be OFF. If LEDs display do not match, refer to user
manual for details.

Power LED

State

Description

Corrective Actions

Green LED

Power is on and
CME-LW01 works

LED is OFF

Power on or program is
abnormal

1. Check if power is 24V or

plug is loose.

2. Check if flash memory IC is

well-inserted to the socket.

SP LED

State

Description

Corrective Actions

Green LED

It communicates to AC
drive

Blinked Green

LED

CME-LW01 reads default
setting from AC drive

Red LED

Disconnect or time-out

1. Check if cable is loose.
2. Check if the communication

protocol is properly set.

Service LED

State

Description

Corrective Actions

LED blinks at

1/2 Hz rate

This is the normal

situation for an
un-configured device

LED is OFF

Bad hardware device

Check if anything wrong with

power supply, clock or
Neuron chip.

LED is ON

continuously,
even when
power is first
applied to the
device.

Bad hardware device

1. Check if anything wrong

with power supply, clock or
Neuron chip.

2. Check if there is a short

circuit between pin 17 and
18.

LED blinks at

power-up,
goes OFF,
then ON
solid.

This is the normal

situation for an
application-less device.

If the device is not an

application-less, then it could
be memory problems or
application code errors. A
self-test failure can also turn
the LED ON solid.

NOTE

Please download the XIF file and user manual at